Goodrive350 series high-performance multifunction VFD
Product overview
-9-
R
S
T
U
V
W
(
+
)
(
-
)
DC reactor
P1
PE
PE
Figure 3-3 380V (132kW and higher) main circuit diagram
R
S
T
U
V
W
(
+
)
(
-
)
DC reactor
P1
PE
PE
Figure 3-4 660V main circuit diagram
Note:
The 380V 132kW and higher VFD models can be connected to external DC reactors. Before
connection, remove the copper bar between P1 and (+). The 380V 132kW and higher VFD
models can be connected to external braking units. DC reactors and braking units are optional
parts.
The 380V 18.5kW
–110kW (inclusive) VFD models are equipped with built-in DC reactors, while
the 380V 355kW and higher are equipped with built-in AC input reactors.
The 380V 37kW and lower VFD models are equipped with built-in braking units, which are
optional for the 45kW
–110kW (inclusive) models. The models with built-in braking units can be
connected to external braking resistors. Braking resistors are optional parts.
The 660V VFD models can be connected to external DC reactors. Before connection, remove the
copper bar between P1 and (+). These models can be connected to external braking units. DC
reactors and braking units are optional parts. The 660V 400kW and higher VFD models are
equipped with built-in AC input reactors.