Goodrive350 series high-performance multifunction VFD
Function parameter list
-268-
Function
code
Name
Description
Default Modify
0: Disable
1: Enable
P28.24
Enabling digital
calibration in EC
PT100/PT1000
temperature
detection
0
–4
0: Disable
1: Enable PT100 lower limit digital calibration.
2: Enable PT100 upper limit digital calibration.
3: Enable PT1000 lower limit digital calibration.
4: Enable PT1000 upper limit digital calibration.
0
○
P28.25
Type of sensor
for AI/AO card to
detect motor
temperature
0
–3
0: No temperature sensor
1: PT100
2: PT1000
3: KTY84
4: PTC (Measuring resistance only)
Note:
Temperature is displayed through P19.11.
To measure temperature, switch the output of AO1
to current, and connect one end of the
temperature resistor to AI1 and AO1, and the other
end to GND.
0
◎
P28.26
AI/AO detected
motor OH
protection
threshold
0.0
–200.0°C
Note:
When the motor temperature exceeds the
threshold, the VFD releases the OT alarm.
110.0°C
○
P28.27
AI/AO detected
motor OH
pre-alarm
threshold
0.0
–200.0°C
Note:
When the motor temperature exceeds the
value, the DO terminal with function 48 (AI
detected motor OH pre-alarm) outputs a valid
signal.
90.0°C
○
P90
––
Tension control in speed mode
Function
code
Name
Description
Default Modify
P90.00
Tension control
mode
0: Invalid
1: Speed mode
2: Open-loop torque mode
3: Closed-loop torque mode
Note:
The value 0 indicates tension control is
invalid. Select a non-0 value to enable the tension
control function.
0
◎