Goodrive350 series high-performance multifunction VFD
Function parameter list
-191-
Function
code
Name
Description
Default
value
Modify
terminal control
setup
Ones: Frequency control selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step
speed takes priority
Hundreds: Action selection during stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
P08.45
UP terminal
frequency
incremental
integral rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.46
DOWN terminal
frequency
decremental
change rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection
for frequency
setup during
power down
0x000
–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus/Modbus TCP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through DP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
0x000
○
P08.48
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power consumption=P08.48×1000+
P08.49
0kWh
○