![INVT GD350-004G-4 Operation Manual Download Page 190](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703190.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-181-
Function
code
Name
Description
Default
value
Modify
STOP/RST key situation.
0: valid only for panel control only
1: valid for both panel and terminal control
2: valid for both panel and communication control
3: valid for all control modes
P07.05
–
P07.07
Reserved
/
/
/
P07.08
Frequency
display
coefficient
0.01
–10.00
Display frequency=running frequency× P07.08
1.00
○
P07.09
Speed display
coefficient
0.1
–999.9%
Mechanical speed=120×display running
frequency×P07.09/number of motor pole pairs
100.0%
○
P07.10
Linear speed
display
coefficient
0.1
–999.9%
Linear speed=mechanical speed×P07.10
1.0%
○
P07.11
Temperature of
rectifier bridge
module
-20.0
–120.0°C
0.0°C
●
P07.12
Temperature of
inverter module
-20.0
–120.0°C
0.0°C
●
P07.13
Software version
of control board
1.00
–655.35
Depends
on
version
●
P07.14
Accumulated
running time
0
–65535h
0h
●
P07.15
High bit of VFD
power
consumption
Display the power consumption of the VFD.
VFD power consumption=P07.15×1000+P07.16
Setting range of P07.15: 0
–65535 kWh (×1000)
Setting range of P07.16: 0.0
–999.9 kWh
0kWh
●
P07.16
Low bit of VFD
power
consumption
0.0kWh
●
P07.17
Reserved
/
/
/
P07.18
Rated power of
VFD
0.4
–3000.0kW
Depends
on model
●
P07.19
Rated voltage of
VFD
50
–1200V
Depends
on model
●
P07.20 Rated current of 0.1
–6000.0A
Depends
●