Goodrive350 series high-performance multifunction VFD
Function parameter list
-203-
Function
code
Name
Description
Default
value
Modify
accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0
–200.0% (of the
rated VFD output current)
Setting range of P11.07: 0.00
–50.00Hz/s
P11.08
VFD or motor
overload/underlo
ad pre-alarm
0x000
–0x1132
Ones place:
0: Motor overload/underload pre-alarm, relative to
rated motor current
1: VFD overload/underload pre-alarm, relative to
rated VFD output current
2: VFD output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The VFD continues running after
overload/underload alarm.
1: The VFD continues running after underload
alarm, and stops running after overload fault.
2: The VFD continues running after overload
alarm, and stops running after underload fault.
3: The VFD stops running after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current reference
selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
0x000
○