![INVT GD350-004G-4 Operation Manual Download Page 234](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703234.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-225-
Function
code
Name
Description
Default
value
Modify
12: AO1 output setting 1 (-1000
–+1000, in which
1000 corresponds to 100.0%)
13: AO2 output setting 2 (-1000
–1000, in which
1000 corresponds to 100.0%)
14: High-order bit of position reference (signed)
15: Low-order bit of position reference (unsigned)
16: High-order bit of position feedback (signed)
17: Low-order bit of position feedback (unsigned)
18: Position feedback setting flag (position
feedback can be set only after this flag is set to 1
and then to 0)
19: Function parameter mapping (PZD2
–PZD12
correspond to P14.49
–P14.59)
20
–31: Reserved
P16.43
Sent PZD2
0
–31
0: Invalid
1: Running frequency (x100, Hz)
2: Set frequency (x100, Hz)
3: Bus voltage (x10, V)
4: Output voltage (x1, V)
5: Output current (x10, A)
6: Actual output torque (x10, %)
7: Actual output power (x10, %)
8: Rotation speed of running (x1, RPM)
9: Linear speed of running (x1, m/s)
10: Ramp reference frequency
11: Fault code
12: AI1 input (x100, V)
13: AI2 input (x100, V)
14: AI3 input (x100, V)
15: HDIA frequency value (x100, kHz)
16: Terminal input status
17: Terminal output status
18: PID reference (x100, %)
19: PID feedback (x100, %)
20: Motor rated torque
21: High-order bit of position reference (signed)
22: Low-order bit of position reference (unsigned)
23: High-order bit of position feedback (signed)
0
○
P16.44
Sent PZD3
0
○
P16.45
Sent PZD4
0
○
P16.46
Sent PZD5
0
○
P16.47
Sent PZD6
0
○
P16.48
Sent PZD7
0
○
P16.49
Sent PZD8
0
○
P16.50
Sent PZD9
0
○
P16.51
Sent PZD10
0
○
P16.52
Sent PZD11
0
○
P16.53
Sent PZD12
0
○