![INVT GD350-004G-4 Operation Manual Download Page 27](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703027.webp)
Goodrive350 series high-performance multifunction VFD
Installation guidelines
-18-
Environment
Condition
Condensation is not allowed.
The max RH cannot exceed 60% in the environment where there are
corrosive gases.
Storage
temperature
-30
–+60°C
Running
environment
The installation site should meet the following requirements.
Away from electromagnetic radiation sources.
Away from oil mist, corrosive gases and combustible gases.
Ensure foreign object like metal powder, dust, oil and water will not fall
into the VFD (do not install the VFD onto combustible object like wood).
Away from radioactive substance and combustible objects
Away from harmful gases and liquids
Low salt content
No direct sunlight
Altitude
Below 1000m.
When the altitude exceeds 1000m, derate 1% for every additional 100m.
When the installation site altitude exceeds 3000m, consult the local INVT
dealer or office.
Vibration
Max. vibration acceleration: 5.8m/s
2
(0.6g)
Installation
direction
You are recommended to install the VFD vertically to ensure good heat
dissipation effect.
Note:
The VFD must be installed in a clean and well-ventilated environment based on the IP rating.
The cooling air must be clean enough and free from corrosive gases and conductive dust.
4.2.2 Installation direction
The VFD can be installed on the wall or in a cabinet.
The VFD must be installed vertically. Check the installation position according to following
requirements. See Appendix C Dimension drawings.
OK
NG
NG
A. Vertical installation
B. Horizontal installation
C. Transverse installation
Figure 4-1 Installation direction of the VFD