GVX9000 AF Drives

 

User Manual 

New Information
June 2006

Summary of Contents for GVX9000

Page 1: ...MN04000001E For more information visit www EatonElectrical com GVX9000 AF Drives User Manual New Information June 2006...

Page 2: ......

Page 3: ...ION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton Electrical Inc be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwi...

Page 4: ...ii GVX9000 User Manual This page intentionally left blank...

Page 5: ...ns 1 4 CHAPTER 2 OVERVIEW OF THE GVX9000 DRIVE 2 1 Receiving and Inspection 2 2 Nameplate Information 2 2 Catalog Number 2 3 Style Number 2 4 External Parts and Label Locations 2 4 Digital Keypad Oper...

Page 6: ...ewing and Changing Parameter Settings 5 2 Parameter Groups 5 4 Group 20 Easy Mode Settings 5 5 Group 30 Inputs 5 6 Explanations Digital Input Terminal 5 11 Group 40 Outputs 5 24 Function Explanations...

Page 7: ...nsions for Braking Resistors C 8 EMI Filter Cross Reference C 9 Keypad Remote Mounting Kit P N GVXRM C 19 APPENDIX D DIMENSIONS D 1 Digital Keypad D 2 Drives D 3 APPENDIX E EASY MODE SETTINGS E 1 Choo...

Page 8: ...Flow in Inches mm 4 3 Figure 5 1 Page Groups 5 2 Figure 5 2 Parameter Groups 5 2 Figure 5 3 Parameter Setting 5 3 Figure 5 4 Scrolling Parameters 5 3 Figure 5 5 Programming Mode 5 3 Figure 5 6 Paramet...

Page 9: ...tion 5 56 Figure 5 42 I2 t Curves 5 58 Figure 5 43 Output Voltage Adjustment 5 59 Figure C 1 GBM2022 GBM4045 GBM5055 Braking Unit C 6 Figure C 2 Approximate Dimensions in Inches mm RF022B21BA RF037B43...

Page 10: ...2 30 Inputs B 2 Table B 3 40 Outputs B 5 Table B 4 50 AC Drive Control B 7 Table B 5 60 Motor Control B 13 Table B 6 70 Protective Functions B 14 Table B 7 80 Keypad Display B 16 Table B 8 90 Communi...

Page 11: ...tentially hazardous situation which if not avoided can result in minor to moderate injury or serious damage to the product The situation described in the CAUTION may if not avoided lead to serious res...

Page 12: ...htened to the proper torque rating shown in Table 3 3 WARNING This equipment should be installed adjusted and serviced by qualified electrical maintenance personnel familiar with the construction and...

Page 13: ...n the inverter housing such as wire clippings spatter from welding metal shavings dust etc Otherwise there is the danger of fire CAUTION Be sure not to install or operate an inverter which is damaged...

Page 14: ...ter can be easily changed from low speed to high speed Be sure to check the capability and limitations of the motor and machine before operating the inverter Otherwise there is the danger of injury CA...

Page 15: ...anual 1 1 Introduction Chapter 1 Inside this chapter Introduction How to Use This Manual 1 2 Intended Audience 1 3 Conventions Used in This Manual 1 3 Warranty and Liability Information 1 4 Related Pu...

Page 16: ...inspection procedures and provides an introduction to digital keypad operation Chapter 3 Storage and Installation describes planning for drive installation and drive mounting This chapter also include...

Page 17: ...cations throughout this manual Digital Keypad Display The Digital Keypad display is an LCD readout of drive parameter selections and drive operation status Letters or numbers appear in the display acc...

Page 18: ...urning any defective product When purchased through an Authorized Distributor the Distributor should supply an RMA number to their customer The maximum liability of this warranty is limited to the pur...

Page 19: ...the GVX9000 Drive Chapter 2 Inside this chapter Overview of the GVX9000 Drive Receiving and Inspection 2 2 Nameplate Information 2 2 Catalog Number 2 3 Style Number 2 4 External Parts and Label Locati...

Page 20: ...the unit to insure it was not damaged during shipment Make sure that the part number indicated on the nameplate corresponds with the part number of your order Nameplate Information Figure 2 1 Example...

Page 21: ...1 A 1 2 Voltage 2 230V AC 4 460V AC 5 575V AC Enclosure Version Type Motor Horsepower 001 1 hp 0 7 kW 002 2 hp 1 5 kW 003 3 hp 2 2 kW 005 5 hp 3 7 kW 007 7 1 2 hp 5 5 kW 010 10 hp 7 5 kW 015 15 hp 11...

Page 22: ...er The style number contains the same information as the Catalog Number and is used internally for ordering purposes External Parts and Label Locations Figure 2 2 Parts and Label U T1 V T2 W T3 R L1 1...

Page 23: ...th exit from parameter edit mode STOP RESET This button has two integrated operations The button operates as Stop button for normal operation In the parameter edit mode it is used to cancel previous a...

Page 24: ...in parameter edit mode exits mode backs up one step cancels edited parameter exit from a parameter edit mode RIGHT Arrow navigation button movement to right enter parameter group mode enter parameter...

Page 25: ...rage 3 2 Environment 3 2 Operation 3 2 Storage 3 2 Transportation 3 2 Pollution Degree 3 2 Mounting Area 3 3 Wiring 3 4 Applicable Codes 3 4 Basic Wiring Diagram 3 5 External Wiring 3 8 Control Termin...

Page 26: ...n Air Temperature 1 hp 100 hp 10 to 50 C 14 to 122 F Relative Humidity 0 to 90 no condensation allowed Atmosphere Pressure 86 to 106 kPa Installation Site Altitude below 1000m Vibration Maximum 9 80 m...

Page 27: ...ases or liquids or airborne dust or metallic particles Mount the AC drive vertically and do not restrict the air flow to the heatsink fins The AC drive generates heat Allow sufficient space around the...

Page 28: ...ctive 93 68 EEC Digital Keypad the following AC Motor Drives GVX001A1 2 GVX002A1 2 GVX003A1 2 GVX005A1 2 GVX007A1 2 GVX010A1 2 GVX015A1 2 GVX020A1 2 GVX025A1 2 GVX030A1 2 GVX040A1 2 GVX050A1 2 GVX001A...

Page 29: ...DC 2mA Motor Analog Signal Common RA3 Factory Setting Freq Setting Indication 48V50mA Factory Setting Warning Factory Setting Fault Indication 48V50mA Factory Setting Drive Running Digital Output Comm...

Page 30: ...al Common RA3 Factory Setting Freq Setting Indication 48V50mA Factory Setting Warning Factory Setting Fault Indication 48V50mA Factory Setting Drive Running Digital Output Common Sw1 Sink Source Facto...

Page 31: ...Leads Cable D1 D2 D3 D4 D5 D6 D7 D9 D10 D8 COM RUN STOP REV FWD E F Multi Step 1 Multi Step 2 Multi Step 3 Multi Step 4 Factory Setting Don t apply the mains voltage directly to above terminals E Res...

Page 32: ...ke Braking Unit Braking Resistor FUSE NFB Power Supply Output AC Line Reactor EMI Filter Motor Magnetic Contactor Input AC Line Reactor R L1 S L2 T L3 1 2 U T1 V T2 W T3 DC Choke Braking Unit FUSE NFB...

Page 33: ...onal Please do not use a Magnetic Contactor as the ON OFF switch of the AC drive this will reduce the operating life of the AC drive The contactor should only be used as a safety device for disconnect...

Page 34: ...y Setting Warning Digital Output Factory Setting Frequency Setting Indication Factory Setting Fault Indication NC Relay Output Factory Setting Drive Running NO Relay Output NO Relay Output DPO COM AI1...

Page 35: ...munication port RS 485 serial communication interface 10V A 10V power supply AI1 A Analog voltage input 1 0 10V input AI2 A Analog voltage input 2 4 20 mA input AI3 A Analog voltage input 3 10 to 10V...

Page 36: ...3 12 GVX9000 User Manual Storage and Installation Figure 3 10 Main Circuit 7 1 2 to 15 hp B2 POWER R L1 T L3 S L2 1 2 B1 W T3 MOTOR U T1 IM 3 V T2 Model GVX007A1 2 GVX010A1 2 GVX015A1 2 GVX007A1 4 GV...

Page 37: ...GVX9000 User Manual 3 13 Storage and Installation Figure 3 11 Main Circuit 20 to 30 hp DC DC POWER T L3 S L2 R L1 1 2 MOTOR V T2 U T1 W T3 IM 3 IM 3 Model GVX020A1 2 GVX025A1 2 GVX030A1 2 GVX020A1 4 G...

Page 38: ...Main Circuit Wiring 3 14 GVX9000 User Manual Storage and Installation Figure 3 12 Main Circuit 40 to 50 hp 460V IM 3 POWER MOTOR R L1 1 2 S L2 T L3 U T1 V T2 W T3 Model GVX040A1 4 GVX050A1 4...

Page 39: ...al 3 15 Storage and Installation Figure 3 13 Main Circuit 40 to 50 hp 230V 60 to 100 hp 460V POWER IM 3 MOTOR 173in lbf Screw Torque 200kgf cm W T3 S L2 R L1 T L3 2 1 U T1 V T2 Model GVX060A1 4 GVX075...

Page 40: ...2 240V 25 hp 240V 30 hp 240V 40 hp 240V 50 hp 75 75 90 90 110 120 142 145 3 26 7 2 33 6 1 0 53 5 3 0 85 30 26 0 Use Terminal 30 26 0 Use Terminal 200 173 6 200 173 6 GVX001A1 4 GVX002A1 4 GVX003A1 4 G...

Page 41: ...9000 ground terminals may also be connected in parallel as shown in the Figure 3 14 Make sure there are no ground loops Figure 3 14 Parallel Grounding When the AC drive output terminals U T1 V T2 and...

Page 42: ...where a load reactor is needed install the filter close to U T1 V T2 W T3 side of AC drive Do not use a Capacitor or L C Filter Inductance Capacitance or R C Filter Resistance Capacitance unless appr...

Page 43: ...tion 4 2 Mounting Location 4 2 Inverter Mounting 4 4 Wiring Preparation 4 4 Wire Sizes 4 5 Fuses and Circuit Breakers 4 6 Fusing 4 6 Manual Motor Starters UL489 Circuit Breakers 4 6 Wiring the Inverte...

Page 44: ...on Step 1 Study the following caution messages associated with mounting the inverter WARNING This equipment should be installed adjusted and serviced by qualified electrical maintenance personnel fami...

Page 45: ...operate an inverter which is damaged or has missing parts Otherwise it may cause injury to personnel CAUTION Be sure to install the inverter in a well ventilated room which does not have direct exposu...

Page 46: ...ing Step 4 Locate the applicable drawing in the Appendix for the inverter unit Dimensions are given in inches millimeters format Note Some inverter housings require two mounting screws while others re...

Page 47: ...circuit breaker to be used Note 3 Be sure to use larger wires for the power lines in the distance exceeds 20 meters Motor Output kW hp Inverter Model Wiring kW hp Power Lines Signal Lines 0 75 1 5 2 2...

Page 48: ...circuit breaker selection use only the recommended line fuses circuit breakers specified in this section Fusing The GVX9000 has been UL tested and approved for use with input fuses The ratings in Tabl...

Page 49: ...020A1 2 GVX025A1 2 50 60 75 49 65 75 150 200 225 JJN 150 JJN 200 JJN 225 Consult factory Consult factory GVX030A1 2 GVX040A1 2 GVX050A1 2 90 110 142 90 120 145 300 350 450 JJN 300 JJN 350 JJN 450 Cons...

Page 50: ...inverter and or overtemperature faults Note Contact Eaton for 575V information Voltage Class 230V Class Model No GVX XXXA1 2 001 002 003 005 007 010 015 020 025 030 040 050 Watt Loss at rated current...

Page 51: ...ble power source types For inverters which can accept single phase power use terminals L1 and L2 CAUTION Be sure that the input voltage matches the inverter specifications Single Three phase 200 to 24...

Page 52: ...AC reactor accessory if the wiring between the inverter and motor exceeds 30 feet 10 meters in length Connect the motor to the terminals indicated on the inverter The terminals are labeled T1 T2 and...

Page 53: ...instructions and messages before proceeding with the power up test 1 The power supply must have fusing suitable for the load Check the fuse size chart presented in Table 4 1 if necessary 2 Be sure you...

Page 54: ...TOP LOC FWD LEDs will illuminate If the motor starts running unexpectedly or any other problem occurs press the STOP button Only if necessary should you remove power to the inverter as a remedy Note I...

Page 55: ...ing Parameter Settings 5 2 Parameter Groups 5 4 Group 20 Easy Mode Settings 5 5 Group 30 Inputs 5 6 Explanations Digital Input Terminal 5 11 Group 40 Outputs 5 24 Function Explanations 5 26 Group 50 A...

Page 56: ...ameter Settings Parameters are grouped in a page arrangement Each page will contain a list of the parameters associated with that group Move into the page groups from the display menu by using the rig...

Page 57: ...gure 5 4 Scrolling Parameters Use the ENTER key to enter the programming mode The displayed parameter will flash indicating the parameter can be changed Figure 5 5 Programming Mode RUN STOP FWD REV LO...

Page 58: ...parameter number will again be displayed Note Some parameters cannot be changed while in the RUN START mode Figure 5 6 Parameter Changes To exit the programming mode press the left arrow key to retur...

Page 59: ...peed Command 09 Closed Loop Vector Control This parameter will automatically set the GVX9000 parameters to the most common settings for each application listed options 1 9 The parameters that have bee...

Page 60: ...his parameter sets the command frequency related to 30 01 30 04 A1 Minimum Output Frequency Range 400 0 to 400 0 Hz Default 0 0 Unit 0 1 This parameter sets the command frequency related to 30 02 30 0...

Page 61: ...Maximum Input Voltage 10 10V Range 10 00 to 10 00V Default 10 00V Unit 0 01 This parameter sets the maximum input voltage on terminal A3 30 12 A3 Minimum Input Voltage 10 10V Range 10 00 to 10 00V De...

Page 62: ...o 10 00 sec Default 0 05 sec Unit 0 01 sec This parameter sets the analog input filter time for terminal A3 30 19 Analog Input Frequency Resolution Range 00 to 01 Default 01 00 0 01 Hz 01 0 1 Hz This...

Page 63: ...rnal Fault NO EF 02 External Fault NC EF 03 External Reset NO 04 External Reset NC 05 Preset Speed Switch 1 06 Preset Speed Switch 2 07 Preset Speed Switch 3 08 Preset Speed Switch 4 09 Jog REV STOP F...

Page 64: ...8 Parameter Lock 19 Acceleration Deceleration Inhibit 20 Run Enable 21 PAUSE NO 22 PAUSE NC 23 PID Disable 24 Counter input 25 Counter reset 26 Auxiliary Motor 1 Output Failure 27 Auxiliary Motor 2 Ou...

Page 65: ...al operation will resume after the External Fault is cleared and the AC drive is reset Figure 5 8 Digital Input Terminal Settings 01 02 30 25 Digital Input Terminal D7 Range See Parameter 30 21 Defaul...

Page 66: ...These four inputs select the preset speeds defined by 30 31 to 30 45 Switch 1 Switch 2 Switch 3 Switch 4 30 31 ON OFF OFF OFF 30 32 OFF ON OFF OFF 30 33 ON ON OFF OFF 30 34 OFF OFF ON OFF 30 35 ON OF...

Page 67: ...FF OFF Frequency Master Speed 30 31 30 32 30 33 30 34 30 35 30 42 30 43 1 30 44 30 45 Jog Freq 50 40 30 36 30 37 30 38 Multi Step Speed via External Terminals 30 41 30 40 30 39 D3 D2 D1 D6 D5 D4 D9 D8...

Page 68: ...5 12 Digital Input Terminal Settings 10 11 Settings 12 13 14 Used to select the Operation Command location of the AC drive Figure 5 13 Digital Input Terminal Settings 12 13 14 09 Jog D3 D2 D1 D6 D5 D4...

Page 69: ...t Terminal Settings 15 16 Setting 17 A digital input may be used to select direction Figure 5 15 Digital Input Terminal Setting 17 Setting 18 A digital input terminal may be used to disable users from...

Page 70: ...Digital Input Terminal Setting 19 Setting 20 A digital input may be used to Enable or Disable the RUN command Used as a Safety device Figure 5 18 Digital Input Terminal Setting 20 19 Acceleration Dece...

Page 71: ...nize with the motor speed and then accelerate to Master frequency Figure 5 19 Digital Input Terminal Settings 21 22 Setting 23 Allows an input terminal to disable PID operation as shown in Figure 5 20...

Page 72: ...r unit of material See the diagram below Figure 5 21 Digital Input Terminal Setting 24 24 Counter Input 2 ms 2 ms Indication value trigger enable Counter trigger signal Multi function input terminal S...

Page 73: ...23 Refer to 50 73 to 50 76 Figure 5 23 Digital Input Terminal Settings 26 27 28 Settings 29 30 A digital input may be used to shut the output off pause and not display a fault Figure 5 24 Digital Inpu...

Page 74: ...er to 30 48 to 30 50 Figure 5 26 Digital Input Terminal Setting 32 Settings 33 34 A digital input may be used as an External Emergency Stop Forced Stop This is not a fault condition rather the highest...

Page 75: ...e for the GVX9000 internal counter The counter is incremented by a low to high transition on a Digital Input Terminal D3 to D10 The count will start at C01 A selected Digital Relay Output Terminal may...

Page 76: ...41 Preset Speed 11 Range 0 00 to 400 00 Hz Default 0 00 Hz Unit 0 01 Hz 30 42 Preset Speed 12 Range 0 00 to 400 00 Hz Default 0 00 Hz Unit 0 01 Hz 30 43 Preset Speed 13 Range 0 00 to 400 00 Hz Default...

Page 77: ...ar box ratio Example If your gear box is a 4 1 then enter 4 The function only works with whole ratios 30 49 Index Angle for Simple Index Function Range 0 0 to 360 0 Deg Default 180 Units 0 1 degrees T...

Page 78: ...proportional to the selection made in 40 01 If setting 00 is chosen the analog output voltage on AO to A is directly proportional to the output frequency of the AC drive With 40 02 set at 100 the Maxi...

Page 79: ...10 Over voltage supervision 11 Over heat supervision 12 Over current stall supervision 13 Over voltage stall supervision 14 Final Count value attained 15 Midpoint Count value attained 16 Reverse direc...

Page 80: ...tput frequency is above the desired frequency 08 Below Desired Frequency 40 07 The output terminal will be active when the output frequency is below the desired frequency 09 PID Supervision 10 Over Vo...

Page 81: ...e output terminal will be active when an E Stop is received 26 Desired Frequency Attained 2 The output terminal will be active when 40 09 is reached 27 Soft braking signal The output terminal will be...

Page 82: ...e 01 to 20 Default 00 This parameter changes the number of output pulses on DOP relative to the output frequency DOP to DOC 40 09 Frequency Attained 2 Range 0 00 to 400 00 Hz Default 0 00 Unit 0 01 Hz...

Page 83: ...puts DO1 DO4 is programmed to 33 40 11 Brake Engage Frequency Brake ON Range 0 0 to 400 0 Hz Default 0 0 This parameter selects the frequency when the digital output DO1 DO4 will turn OFF if one of th...

Page 84: ...al keypad on the drive 01 Master Frequency determined by 0 10V on terminal AI1 02 Master Frequency determined by 4 20 mA on terminal AI2 03 Master Frequency determined by 10 10V on terminal AI3 04 Mas...

Page 85: ...communication interface Keypad STOP key is enabled 04 Operating commands determined by the RS 485 communication interface Keypad STOP key is not enabled 50 05 Dual Frequency Input Mode Range 00 to 03...

Page 86: ...C drive stops the output instantly upon command and the motor free spins until it comes to a complete stop 50 09 HOA Stop Method Range 00 to 01 Default 01 00 Ramp 01 Coast This parameter determines ho...

Page 87: ...to 1 00 Hz msec Default 0 01 This parameter determines the speed the command frequency will change when holding down the UP DOWN key 50 14 Maximum Output Frequency Range 50 to 400 0 Hz Default 60 00 T...

Page 88: ...id Point Frequency can be determined This parameter must be equal to or greater than Minimum Output Frequency 50 19 and equal to or less than Motor Nameplate Frequency 50 15 During Vector this paramet...

Page 89: ...s the Minimum Output Voltage of the AC drive V F curve This parameter must be equal to or less than Mid Point Output Voltage 50 18 During Vector this parameter is disabled Figure 5 31 shows three exam...

Page 90: ...orrect encoder count in parameter 60 18 and encoder type 60 19 50 22 CT VT Mode Range Default 00 00 Constant Torque 01 Variable Torque This parameter selects the Torque Mode for the GVX9000 50 23 Vari...

Page 91: ...d for the AC drive to decelerate from the Maximum Output Frequency 50 14 down to 0 Hz The rate is linear unless S Curve is Enabled The second third and fourth acceleration and deceleration times 50 26...

Page 92: ...l 03 Auto Accel Decel 04 Auto Accel Decel Stall Prevention Limited by 50 24 to 50 31 50 34 Acceleration 1 to Acceleration 2 Transition Frequency Range Default 0 0 0 0 Disable Above min freq Enable 0 0...

Page 93: ...matically change from Decel Time 1 to Decel Time 2 This saves Input Points from being used to do the same process 50 36 Acceleration S Curve Range 00 to 07 Default 0 00 Disabled 01 07 Enabled 50 37 De...

Page 94: ...cceleration for Jog operation 50 39 Jog Decel Time Range 0 01 to d 3600 0 sec Default 10 00 Unit Deceleration for Jog operation 50 40 Jog Frequency Range 0 1 to 400 00 Hz Default 6 00 Unit Frequency f...

Page 95: ...rameter enables the AC Motor drive s ability to operate in the reverse direction 50 42 Momentary Power Loss Range Default 0 00 Stop operation after momentary power loss 01 Continue operation after mom...

Page 96: ...parameter also determines the wait time after performing an external PAUSE and Fault Reset function 50 44 Speed Search Maximum Current Range 30 to 200 Default 150 50 45 Speed Search Start Point Range...

Page 97: ...utput Frequency is set at 50 Hz and the Maximum Output Frequency is set at 60 Hz the actual Maximum Output Frequency will be limited to 50 Hz If the Lower limit of Output Frequency is set at 10 Hz and...

Page 98: ...7 Skip Frequency 4 Bandwidth Range 0 0 to 20 00 Hz Default 0 The above eight parameters determine the Skip Frequencies and Bandwidth for the drive to avoid 50 54 to 50 57 determine the frequency band...

Page 99: ...03 Negative AI2 4 20 mA 04 Positive AI3 10 10V This parameter determines the analog PID feedback source and type 50 60 PID P Gain Adjustment Range 0 0 to 10 0 Default 1 0 50 61 PID I Gain Adjustment R...

Page 100: ...8 PID Feedback Deviation Detection Time Range 0 00 to 3600 0 sec Default 1 0 50 69 PID Treatment of the Feedback Deviation Error Range Default 01 00 Warning and Inverter Stop 01 Warning and Continue O...

Page 101: ...motor If the setting is 0 the auxiliary motor cannot be attached 50 74 Frequency Point to Stop Motor 2 Range 0 00 to 400 00 Hz Default 0 00 Unit 0 01 When the output frequency reaches the parameter v...

Page 102: ...g stopping These parameters determine the starting sequence of auxiliary motors The auxiliary motor started first will be stopped first Example Start sequence motor 1 motor 2 motor 3 Stop sequence mot...

Page 103: ...ion This parameter may be set during operation 60 03 Dynamic Tune with Unloaded Motor Range Default 00 00 Disable 01 DC test static test 02 DC test and no load test To conduct the auto tuning feature...

Page 104: ...drive Parameter 50 08 must be set to RAMP to stop for DC braking to be enabled 60 08 DC Brake Frequency Point Range 0 00 to 60 00 Hz Default 0 Unit 0 01 Hz This parameter determines the Frequency Poin...

Page 105: ...ip Compensation Range 0 00 to 10 00 Default 0 An increasing load on an asynchronous motor will cause an increase in motor slip This Slip Compensation parameter may be used to compensate for the nomina...

Page 106: ...Poles Range 2 to 10 Default 4 60 13 Motor Rated Slip Range 0 00 to 20 00 Hz Default 3 00 The parameter determines the motor s rated slip Standard 1800 rpm induction motors have 3 slip If the motor co...

Page 107: ...ng this parameter to 0 0 will disable this function 60 22 CLV Frequency Limit Range 0 0 100 00 Hz Default 10 00 Setting this parameter to 0 0 will disable this function 60 23 CLV Encoder Detection Upd...

Page 108: ...tall Level Over Speed Range 0 115 Default 110 This parameter determines the maximum encoder feedback signal allowed before a encoder feedback fault will occur Pr 60 18 x Pr 50 14 Max feedback frequenc...

Page 109: ...imum allowable value due to motor regeneration When this function is enabled the AC drive will stop decelerating and maintain a constant output frequency The drive will resume deceleration when the vo...

Page 110: ...output frequency The AC drive will only resume acceleration when the current drops below the value set in 70 02 70 03 Over Current Stall Prevention during Operation Range 20 to 200 Default 170 00 Disa...

Page 111: ...of the drive This parameter sets the Over Torque Detection level in 1 increments The AC drive rated current is equal to 100 70 06 Over Torque Detection Time Range 0 1 to 10 0 sec Default 0 1 Unit 0 1...

Page 112: ...oltage is varying between 200V to 264V AC the drive s output voltage will automatically be limited to 200V AC Without AVR function the Motor Nameplate Voltage may vary between 180V to 264V AC due to t...

Page 113: ...Output fault ramp to Stop 02 Coast stop and restart after delay 70 14 setting time Setting 0 or 1 If the output current falls below 70 11 then the drive will generate an output fault via one of the di...

Page 114: ...1 Fan is off one minute after stop command 2 Fan on with run fan off with stop 3 Fan on when temp limit reached 70 18 Line Start Lock Out Range Default 00 00 Start lockout disabled keep previous statu...

Page 115: ...0 Auto Restart After Fault Range 00 to 10 Default 00 This parameter determines the wait time to reset 70 20 after a fault upon restart 70 21 Reset Time for Auto Restart after Fault Range 0 to 60000 se...

Page 116: ...GVX020A1 2 240V AC 20 hp CT 08 GVX025A1 2 240V AC 25 hp CT 09 GVX030A1 2 240V AC 30 hp CT 10 GVX040A1 2 240V AC 40 hp CT 11 GVX050A1 2 240V AC 50 hp CT 12 Reserved 13 Reserved 14 GVX001A1 4 480V AC 1...

Page 117: ...575V AC 2 hp CT 38 GVX003A1 5 575V AC 3 hp CT 39 GVX005A1 5 575V AC 5 hp CT 40 GVX007A1 5 575V AC 7 1 2 hp CT 41 GVX010A1 5 575V AC 10 hp CT 42 GVX015A1 5 575V AC 15 hp CT 43 GVX020A1 5 575V AC 20 hp...

Page 118: ...07 External Fault 08 CPU failure 1 09 CPU failure 2 10 CPU failure 3 11 Hardware Protection Failure 12 Over current during accel 13 Over current during decel 14 Over current during steady state 15 Gr...

Page 119: ...ultiplier Range 0 01 to 160 00 Default 1 This parameter determines the multiplier used for the User Defined display 80 10 External Terminal Scanning Time Range 01 to 20 Default 1 Unit 2 msec This func...

Page 120: ...Display Range Default 00 00 Display output current 01 Display counter value 02 Display DC BUS voltage 03 Display output voltage 04 Output power factor angle 05 Display output power kW 06 Display actu...

Page 121: ...data bits even parity 1 stop bit 05 Modbus RTU Mode 8 data bits odd parity 1 stop bit 90 02 RS 485 Communication Range 01 to d 254 Default 01 90 03 Transmission Speed Range Default 01 00 4800 baud 01...

Page 122: ...ication of EF and Reset Range Default N A Bit 0 1 EF On Bit 1 1 Reset Bit 2 15 Reserved 90 09 Status Monitor for Error Code Range Default N A 00 No Fault occurred 01 Over current 02 Over voltage 03 Ov...

Page 123: ...ed 90 10 Status Monitor for AC Drive Range Default N A Bit 0 1 00 Stop 01 Decelerate during the drive stopping 10 The drive standby 11 Run Bit 2 1 JOG active Bit 3 4 00 FWD 01 REV to FWD 10 FWD to REV...

Page 124: ...00 to 655 35 Default N A 90 16 Status Monitor for Output Voltage Range 0 0 to Max VAC Default N A 90 17 Status Monitor for Unit Temperature Range 0 0 to Max degree C Default N A 90 18 Status Monitor f...

Page 125: ...fault N A 90 25 AI3 Signal Range 0 00 100 00 Default N A 90 26 PG Pulses Low Word Unit Time Range 00 to 65535 Default N A 90 27 PG Pulses High Word Unit Time Range 00 to 65535 Default N A 90 28 Motor...

Page 126: ...5 72 GVX9000 User Manual Descriptions of Parameter Settings This page intentionally left blank...

Page 127: ...GVX9000 User Manual 6 1 Maintenance and Inspection Chapter 6 Inside this chapter Maintenance and Inspection Periodic Inspection 6 2 Periodic Maintenance 6 2...

Page 128: ...any irregular vibration or sound occurred during the operation Whether the motors are overheating during the operation Note Always check the input voltage of the AC drive with a Voltmeter Periodic Ma...

Page 129: ...GVX9000 User Manual 7 1 Troubleshooting and Fault Information Chapter 7 Inside this chapter Troubleshooting and Fault Information Common Problems and Solutions 7 2 Warning Codes 7 5...

Page 130: ...28 50 30 4 Check for possible excessive loading conditions at the motor 5 If there are any abnormal conditions when operating the AC drive after a short circuit is removed it should be sent back to ma...

Page 131: ...on setting to an appropriate setting Over Current During Accel Over current during acceleration 1 Short circuit at motor output 2 Torque boost too high 3 Acceleration time too short 4 AC drive output...

Page 132: ...input voltage falls within the rated AC drive input voltage Switch on the AC drive External Fault The external terminal DI1 COM goes from OFF to ON When external terminal DI1 COM is closed the drive s...

Page 133: ...d action Communication Time Out Communication time out Over Torque Motor overload Check the parameter settings 70 04 70 06 1 Reduce the motor load 2 Adjust the over torque detection setting to an appr...

Page 134: ...7 6 GVX9000 User Manual Troubleshooting and Fault Information This page intentionally left blank...

Page 135: ...GVX9000 User Manual A 1 Technical Data Appendix A Inside this chapter Technical Data Technical Data A 2...

Page 136: ...6 34 3 45 7 55 0 CT VT Rated Output Current A 5 0 7 0 11 17 25 33 49 65 75 90 120 145 Maximum Output Voltage V 3 Phase Proportional to Input Voltage Output Frequency Hz 0 1 400 Hz Carrier Frequency k...

Page 137: ...9 9 13 7 18 3 24 4 28 9 34 3 45 7 55 6 69 3 84 114 VT Rated Output Capacity kVA 2 3 3 2 4 2 6 5 14 18 25 29 34 46 56 69 84 114 137 CT Rated Output Current A 2 7 4 2 5 5 8 5 13 18 24 32 38 45 60 73 91...

Page 138: ...5 7 5 10 13 4 18 9 21 9 26 9 33 9 40 8 51 8 61 7 79 7 99 6 Rated Output Current A 1 7 3 5 4 5 7 5 10 13 5 19 22 27 34 41 52 62 80 100 Maximum Output Voltage V 3 phase Proportional to Input Voltage Ou...

Page 139: ...cation auxiliary motor output overheat alarm emergency stop under current low voltage Analog Output Signal Output frequency current voltage frequency command speed Power factor Other Functions AVR S C...

Page 140: ...A 6 GVX9000 User Manual Technical Data This page intentionally left blank...

Page 141: ...ndix B Inside this chapter Parameter Tables GVX9000 Parameter Listings 20 Easy Mode Settings B 2 30 Inputs B 2 40 Outputs B 5 50 AC Drive Control B 7 60 Motor Control B 13 70 Protective Functions B 14...

Page 142: ...put Voltage 0 10V 0 00 to 10 00V 0 00 0102H 30 03 5 6 A1 Maximum Output Frequency 400 0 to 400 0 Hz 60 00 0103H 30 04 5 6 A1 Minimum Output Frequency 400 0 to 400 0 Hz 0 0 0104H 30 05 5 6 A1 Reverse O...

Page 143: ...05 sec 0112H 30 19 5 8 Analog Input Frequency Resolution 00 0 01 Hz 01 01 0 1 Hz 0113H 30 20 5 8 Digital Input Terminals D1 D2 01 2 wire Operation Mode 1 D1 FWD STOP D2 REV STOP 02 02 2 wire Operation...

Page 144: ...Stop NC 0115H 30 22 5 10 Digital Input Terminal D4 See Parameter 30 21 06 0116H 30 23 5 10 Digital Input Terminal D5 See Parameter 30 21 07 0117H 30 24 5 10 Digital Input Terminal D6 See Parameter 30...

Page 145: ...ency Hz 00 01 Percent 02 User Definition 0 001 max unit Unit set by 30 47 012EH 30 47 5 23 User Definition for 30 46 Option 2 0 001 to 10 000 1 000 012FH 30 48 5 23 Gear Ratio for Simple Index Functio...

Page 146: ...Over heat supervision 12 Over current stall supervision 13 Over voltage stall supervision 14 Final Count value attained 15 Midpoint Count value attained 16 Reverse direction notification command 17 U...

Page 147: ...12 5 29 EF Displayed at Midpoint Count 00 Disabled 00 01 Display EF when midpoint count is reached Table B 4 50 AC Drive Control Modbus Groups Page Parameter Description Range Default User Settings 03...

Page 148: ...RS 485 Frequency not retained 0302H 50 03 5 30 Source of LOCAL HAND Operation Command 00 Operating commands determined by the Digital Keypad 00 01 Operating commands determined by the External Contro...

Page 149: ...06 5 31 Trim Reference 0 00 to 100 00 0 00 0306H 50 07 5 31 Keypad Frequency Setting 50 00 to 400 00 Hz 60 00 0307H 50 08 5 32 Stop Method 00 STOP Ramp EF Coast 00 01 STOP Coast EF Coast 02 STOP Ramp...

Page 150: ...01 V F Closed Loop 02 Sensorless Vector SV 03 Vector Closed Loop CLV 0315H 50 22 5 36 CT VT Mode 00 Constant Torque 00 01 Variable Torque 0316H 50 23 5 36 Variable Torque Curve Selection 00 V F curve...

Page 151: ...og Accel Time 0 01 to d 3600 0 sec 10 00 0326H 50 39 5 40 Jog Decel Time 0 01 to d 3600 0 sec 10 00 0327H 50 40 5 40 Jog Frequency 0 1 to 400 00 Hz 6 00 0328H 50 41 5 41 Reverse Operation 00 Enable Re...

Page 152: ...33AH 50 59 5 45 PID Feedback Source and Type 00 Positive AI1 0 10V 0 01 Negative AI1 0 10V 02 Positive AI2 4 20 mA 03 Negative AI2 4 20 mA 04 Positive AI3 10 10V 033BH 50 60 5 45 PID P Gain Adjustment...

Page 153: ...est 0403H 60 04 5 49 Stator Resistance Calculated Via Auto Tune or Entered Manually 00 to 65535 Ohms 0 0404H 60 05 5 49 DC Brake Current Level 00 to 100 0 0405H 60 06 5 50 DC Brake Time Upon a Start 0...

Page 154: ...0 0419H 60 26 5 54 CLV Encoder Feedback Filter 00 Disable 00 0 002 1 00 041AH 60 27 5 54 CLV Encoder Slip Range Deviation Range 0 0 50 0 10 0 041BH 60 28 5 54 CLV Encoder Stall Level Over Speed 0 115...

Page 155: ...70 09 5 58 Auto Voltage Regulation AVR 00 AVR enabled 00 01 AVR disabled 02 AVR disabled during decel 03 AVR disabled during stop 0509H 70 10 5 59 Auto Energy Saving Operation 00 Disable 00 01 Enable...

Page 156: ...nd source 03 Start lockout enabled change according to the new operation command source 0512H 70 19 5 61 Brake Chopper ON Voltage 230V Series 370 430V DC 380 460V Series 740 860V DC 760 575V Series 66...

Page 157: ...09 GVX030A1 2 240V AC 30 hp CT 10 GVX040A1 2 240V AC 40 hp CT 11 GVX050A1 2 240V AC 50 hp CT 12 Reserved 13 Reserved 14 GVX001A1 4 480V AC 1 hp CT 15 GVX002A1 4 480V AC 2 hp CT 16 GVX003A1 4 480V AC...

Page 158: ...V AC 2 hp CT 38 GVX003A1 5 575V AC 3 hp CT 39 GVX005A1 5 575V AC 5 hp CT 40 GVX007A1 5 575V AC 7 1 2 hp CT 41 GVX010A1 5 575V AC 10 hp CT 42 GVX015A1 5 575V AC 15 hp CT 43 GVX020A1 5 575V AC 20 hp CT...

Page 159: ...t circuit 22 Loss of 4 20 mA 23 Under Current Detected 24 Encoder Fault 25 Feedback Deviation Err 26 Count Attained 0607H 80 08 5 65 Power Up Display Selection Also Order of Appearance When Scrolling...

Page 160: ...610H 80 17 5 66 Content of Multifunction Display 00 Display output current 00 01 Display counter value 02 Display DC BUS voltage 03 Display output voltage 04 Output power factor angle 05 Display outpu...

Page 161: ...nication 01 to d 254 01 0702H 90 03 5 67 Transmission Speed 00 4800 baud 01 01 9600 baud 02 19200 baud 03 38400 baud 0703H 90 04 5 67 Transmission Fault Treatment 00 Display fault and Continue operati...

Page 162: ...dware Protection Failure 12 Over current during accel 13 Over current during decel 14 Over current during steady state 15 Ground fault or fuse failure 16 Under Voltage 17 3 Phase Input Power Loss 18 P...

Page 163: ...Monitor for Output Frequency 0 0 to 400 0 Hz N A 070CH 90 13 5 70 Status Monitor for Output Current 0 0 to Max Amps N A 070DH 90 14 5 70 Status Monitor for User Defined High Word 00 to 65535 N A 070EH...

Page 164: ...AI3 Signal 0 00 100 00 N A 0719H 90 26 5 71 PG Pulses Low Word Unit Time 00 to 65535 N A 071AH 90 27 5 71 PG Pulses High Word Unit Time 00 to 65535 N A 071BH 90 28 5 71 Motor Speed rpm 00 to 65535 N A...

Page 165: ...ter Accessories Fuse Specification C 2 Wiring C 3 Braking C 4 All Braking Resistors and Braking Units Used in AC Motor Drives C 4 External Brake Unit C 6 Dimensions for Braking Resistors C 8 EMI Filte...

Page 166: ...CE025C10_ XTCE032C10_ XTCE050D10_ GVX015A1 2 GVX020A1 2 GVX025A1 2 50 60 75 49 65 75 150 200 225 JJN 150 JJN 200 JJN 225 Consult factory Consult factory GVX030A1 2 GVX040A1 2 GVX050A1 2 90 110 142 90...

Page 167: ...h of the AC drive this will reduce the operating life of the AC drive The contactor should only be used as a safety device for disconnecting power to the drive Line Load Reactor Optional To improve th...

Page 168: ...3 000034 0861 1 1 1 125 125 125 5 7 1 2 10 3 7 5 5 7 5 2 080 3 111 4 148 400W 40 500W 30 1000W 20 K13 000034 0825 K13 000034 0826 K13 000034 0862 1 2 125 125 125 15 20 25 11 15 18 5 6 186 8 248 10 281...

Page 169: ...than 2 braking units equivalent resistor value of parallel braking unit can t be less than the value in the column Minimum Equivalent Resistor Value for Each AC Drive the right most column in the tabl...

Page 170: ...Braking C 6 GVX9000 User Manual Accessories External Brake Unit Figure C 1 GBM2022 GBM4045 GBM5055 Braking Unit 3 15 80 0 5 12 130 0 4 76 121 0 13 3 3 Rad 7 87 200 0 7 46 189 5...

Page 171: ...720 760 800 830 6V 950 8V Input Rating DC Voltage 200 400V DC 400 800V DC 607 1000V DC Protection Heat Sink Overheat Temperature over 95 C Alarm Output Relay contact 5A 120V AC 28V DC RA RB RC Power...

Page 172: ...38 1 0 75 19 1 CR100 K13 000034 843 CR300 250 250 300 9 00 228 6 3 00 76 2 1 50 38 1 CR300 K13 000034 843 CR300 250 250 300 9 00 228 6 3 00 76 2 1 50 38 1 CR300 K13 000034 844 CR400 150 150 400 12 00...

Page 173: ...022B21BA GVX001A1 2 GVX002A1 2 GVX003A1 2 three phase 20TDT1W4C CTC513113B 2 9 26TDT1W4C GVX005A1 2 20TDT1W4C CTC513113B 2 9 26TDT1W4C GVX001A1 4 GVX002A1 4 GVX003A1 4 GVX005A1 4 RF037B43BA GVX007A1 4...

Page 174: ...VX9000 User Manual Accessories Catalog Number RF022B21BA RF037B43BA Figure C 2 Approximate Dimensions in Inches mm RF022B21BA RF037B43BA 2 36 60 0 1 18 30 0 1 18 30 59 15 11 89 302 0 5 90 150 0 4 33 1...

Page 175: ...nce GVX9000 User Manual C 11 Accessories Catalog Number RF110B43CA Figure C 3 Approximate Dimensions in Inches mm RF110B43CA 7 87 200 0 2 36 60 0 4 72 120 0 15 04 382 0 1 3 33 0 28 7 0 1 02 26 79 20 1...

Page 176: ...mm 26TDT1W4C 1015 AWG 14 G Y 1015 AWG 14 Blue 1015 AWG 14 Black 1015 AWG 14 Brown S L2 T L3 R L1 Power In 1 97 08 50 0 2 C B M5 x 0 8 4 Places 39 10 0 31 8 0 Dia 4 Places 18 4 5 Rad 12 3 0 Rad 11 18...

Page 177: ...2 T L3 R L1 Power In M4 x 0 7 Typ 4 Places 28 x 39 7 0 x 10 0 Typ 2 Places 28 7 0 Typ 2 Places M6 x 1 0 Typ 4 Places 1015 AWG 10 Y G 1015 AWG 10 Blue 1 18 30 0 1 57 40 0 1 57 40 0 1 57 40 0 79 20 0 79...

Page 178: ...ure C 6 Approximate Dimensions in Inches mm 100TDS84C M8 x 1 25 Typ 6 Places 30 x 49 7 5 x 12 5 Typ 4 Places 14 57 08 370 0 2 0 13 86 352 0 Max H 5 91 04 150 0 1 0 G 7 95 04 202 0 1 0 Max C 4 80 122 0...

Page 179: ...ure C 7 Approximate Dimensions in Inches mm 150TDS84C M8 x 1 25 Typ 6 Places 30 x 49 7 5 x 12 5 Typ 4 Places 16 54 08 420 0 2 0 15 83 402 0 Max H 5 91 04 150 0 1 0 G 7 95 04 202 0 1 0 Max 17 32 440 0...

Page 180: ...ure C 8 Approximate Dimensions in Inches mm 180TDS84C M8 x 1 25 Typ 6 Places 30 x 49 7 5 x 12 5 Typ 4 Places 16 54 08 420 0 2 0 15 83 402 0 Max H 5 91 04 150 0 1 0 G 7 95 04 202 0 1 0 Max 17 32 440 0...

Page 181: ...mm 20TDT1W4C 1015 AWG 16 G Y 1015 AWG 16 Blue 1015 AWG 16 Black 1015 AWG 16 Brown S L2 T L3 R L1 Power In 1 97 08 50 0 2 C B M5 x 0 8 4 Places 39 10 0 31 8 0 Dia 4 Places 18 4 5 Rad 12 3 0 Rad 11 18...

Page 182: ...200TDDS84C Figure C 10 Approximate Dimensions in Inches mm 200TDDS84C 59 15 0 12 Places M8 x 05 1 2 2 Places 26 x 31 6 5 x 8 0 4 Places 24 6 0 4 Places 38 39 975 0 Ref 42 52 1080 0 Ref 37 40 950 0 Re...

Page 183: ...m RUN STOP FWD REV LOC REM LOC REV FWD 75 19 0 36 9 1 M4 P 03 7 x 19 4 8 Deep for Mounting Screw Typ 3 Places 2 87 73 0 3 12 79 2 1 57 40 0 4 33 110 0 3 27 83 0 20 5 0 Dia Typ 3 Places Cut Out for the...

Page 184: ...C 20 GVX9000 User Manual Accessories This page intentionally left blank...

Page 185: ...GVX9000 User Manual D 1 Dimensions Appendix D Inside this chapter Dimensions Digital Keypad D 2 Drives D 3...

Page 186: ...nsions Digital Keypad Figure D 1 Digital Keypad Approximate Dimensions in Inches mm M4 P 03 7 x 19 4 8 Deep for Mounting Screw Typ 3 Places 2 87 73 0 3 12 79 2 1 57 40 0 75 19 0 36 9 1 4 33 110 0 3 27...

Page 187: ...REV LOC REM LOC REV FWD WARNING HIGH VOLTAGE WAIT AT LEASTS 10 MINUTES BEFORE OPENING SEE USER S MANUAL FOR OPERATION GVX9000 Sensorless Vector 5 32 135 0 5 91 150 0 6 84 173 7 26 6 5 Dia 26 6 5 Dia 9...

Page 188: ...m 12 72 323 0 11 93 303 0 7 31 185 6 7 88 200 0 28 7 0 Dia 7 75 196 6 RUN STOP FWD REV LOC REM LOC REV FWD WARNING HIGH VOLTAGE WAIT AT LEASTS 10 MINUTES BEFORE OPENING SEE USER S MANUAL FOR OPERATION...

Page 189: ...RUN STOP FWD REV LOC REM LOC REV FWD WARNING HIGH VOLTAGE WAIT AT LEASTS 10 MINUTES BEFORE OPENING SEE USER S MANUAL FOR OPERATION GVX9000 Sensorless Vector 15 12 384 0 15 90 403 8 8 90 226 0 9 84 250...

Page 190: ...EM LOC REV FWD WARNING HIGH VOLTAGE WAIT AT LEASTS 10 MINUTES BEFORE OPENING SEE USER S MANUAL FOR OPERATION GVX9000 Sensorless Vector 23 19 589 0 22 05 560 0 13 19 335 0 14 57 370 0 51 13 0 Dia 71 18...

Page 191: ...gs Choosing Easy Mode 00 Factory Settings E 2 Changed Parameters 01 Basic V F Curve E 2 02 PID Control E 3 03 Preset Speeds E 4 04 Local Remote E 6 05 Hand Off Auto HOA E 7 06 Variable Torque Pump Fan...

Page 192: ...on Command 00 Operating commands determined by the Digital Keypad 00 0307H 50 08 Stop Method 00 STOP Ramp EF Coast 00 030DH 50 14 Maximum Output Frequency 50 to 400 0 Hz 50 00 030EH 50 15 Motor Namepl...

Page 193: ...eter Disable 00 0202H 40 03 Digital Output Terminal Relay A RA1 RA2 RA3 03 Inverter Fault 03 0203H 40 04 Digital Output Terminal Relay B RB1 RB2 09 PID supervision 09 0204H 40 05 Digital Output Termin...

Page 194: ...0344H 50 69 PID Treatment of the Feedback Deviation Error 00 Warning and Inverter Stop 00 01 Warning and Continue Operation Table E 4 03 Preset Speeds Modbus Groups Parameter Description Range Default...

Page 195: ...Master Frequency determined by digital keypad on the drive 00 0302H 50 03 Source of LOCAL HAND Operation Command 01 Operating commands determined by the External Control Terminals Keypad STOP key is e...

Page 196: ...tput Terminal Relay A RA1 RA2 RA3 03 Inverter Fault 03 0203H 40 04 Digital Output Terminal Relay B RB1 RB2 01 Ready 01 0204H 40 05 Digital Output Terminal DO1 05 At speed 05 0205H 40 06 Digital Output...

Page 197: ...utput Terminal Relay A RA1 RA2 RA3 03 Inverter Fault 03 0203H 40 04 Digital Output Terminal Relay B RB1 RB2 01 Ready 01 0204H 40 05 Digital Output Terminal DO1 05 At speed 05 0205H 40 06 Digital Outpu...

Page 198: ...STOP D2 REV FWD 02 0114H 30 21 Digital Input Terminal D3 14 Control Location Remote Local Remote close for remote 14 0115H 30 22 Digital Input Terminal D4 20 Run Enable 20 0116H 30 23 Digital Input T...

Page 199: ...1 to 50V 1 7 460V Series 0 1 to 100V 3 4 575V Series 0 1 to 637V 4 8 0315H 50 22 CT VT Mode 01 Variable Torque 01 0316H 50 23 Variable Torque Curve Selection 01 1 5 Power curve 01 032FH 50 48 Upper Fr...

Page 200: ...00 Hz 0 50 0313H 50 20 Minimum Output Voltage 230V Series 0 1 to 50V 1 7 460V Series 0 1 to 100V 3 4 575V Series 0 1 to 637V 4 8 0317H 50 24 Acceleration Time 1 0 01 to 600 00 seconds 100 0 0318H 50...

Page 201: ...tion Time 1 0 01 to 600 00 seconds 10 00 0318H 50 25 Deceleration Time 1 0 01 to 600 00 seconds 10 00 032FH 50 48 Upper Frequency Limit Safety 0 01 to 400 00 Hz 60 00 0330H 50 49 Lower Frequency Limit...

Page 202: ...01 to 600 00 seconds 10 00 032FH 50 48 Upper Frequency Limit Safety 0 01 to 400 00 Hz 60 00 0330H 50 49 Lower Frequency Limit Safety 0 0 to 400 00 Hz 0 0410H 60 17 Hunting Coefficient 0 1000 0 0411H 6...

Page 203: ...ual F 1 Declaration of Conformity Appendix F Inside this chapter Declaration of Conformity Low Voltage Directive F 2 EC Declaration of Conformity F 2 Electromagnetic Compatibility F 3 EC Declaration o...

Page 204: ...EC For the evaluation of the compliance with this Directive the following standard was applied The following manufacturer importer is responsible for this declaration AC Motor Drive Product Name GVX00...

Page 205: ...rective the following standard was applied The following manufacturer importer is responsible for this declaration AC Motor Drive Product Name GVX001A1 2 GVX002A1 2 GVX003A1 2 GVX005A1 2 GVX007A1 2 GV...

Page 206: ...F 4 GVX9000 User Manual Declaration of Conformity This page intentionally left blank...

Page 207: ......

Page 208: ...ration is a diversified industrial manufacturer with 2005 sales of 11 1 billion Eaton is a global leader in electrical systems and components for power quality distribution and control fluid power sys...