Summary of Contents for HLP-A Series

Page 1: ......

Page 2: ...HLP A Series...

Page 3: ......

Page 4: ...ronment 11 3 Installation and Direction 11 V Wiring 13 1 Main Circuit Wiring Schematic Diagram 13 2 Description of Terminal Block 14 3 Basic Connection Diagram 16 4 Precautions on Wiring 19 VI Instruc...

Page 5: ...Troubleshooting 82 4 Faults and Analysis 86 XI Selection of Peripheral Devices and Disposition 88 1 Options 88 2 Disposition 89 XII Appendices 93 Appendix 1 Simple Examples of Application 93 Appendix...

Page 6: ...ake sure the safe use of the inverter In case of any doubt please contact our local agent for consultation Our professional persons are willing and ready to serve you The manual is subject to change w...

Page 7: ...mething wrong with the inner parts wiring and circuit board Check if each terminal is tightly locked and if there is any foreign article inside the inverter Check if the operator buttons are all right...

Page 8: ...P A Series 3 2 Nameplate Description of HLP Series Inverter Hardware Version Model HLP A 01D5 43 C Voltage Rating 43 means 3 phase 380V Inverter Capacity 01D5 means 1 5KW Serial No A means A series Tr...

Page 9: ...to line zero Otherwise it will easily cause the protection or errors of the inverter Caution Do not carry the front cover of the inverter directly when handling It should be handled with the base to...

Page 10: ...t be installed because of the requirements of process and others it must be ensured that the inverter has no output when the switch acts In addition it is forbidden to install any capacitor for improv...

Page 11: ...speed limit of the motor bearings and the mechanical devices when the inverter is running at or above the frequency of 50Hz 2 During the Power up Danger Do not plug the connectors of the inverter duri...

Page 12: ...ree phase 220V 50Hz 3 7 6 8 17 3 7 HLPA05D523B One Three phase 220V 50Hz 5 5 10 25 5 5 HLPA07D523B One Three phase 220V 50Hz 7 5 13 2 33 7 5 HLPA001123B One Three phase 220V 50Hz 11 19 6 49 11 HLPA001...

Page 13: ...3 380V 50Hz 30 52 65 30 HLPA003743B 3 380V 50Hz 37 64 80 37 HLPA004543B 3 380V 50Hz 45 72 91 45 HLPA005543B 3 380V 50Hz 55 84 110 55 HLPA007543B 3 380V 50Hz 75 116 152 75 HLPA009043B 3 380V 50Hz 90 13...

Page 14: ...etting Resolution Digital 0 01Hz Analog 1 of Max Operating Frequency Output Resolution 0 01Hz Operator Setting Method Press directly to set Analog Setting Method External Voltage 0 5V 0 10V 4 20mA 0 2...

Page 15: ...tions Overload Protection Electronic relay protection motor Drive for constant torque 150 1 min for the kinds of fan 120 1min FUSE Protection FUSE broken Motor stops Over voltage DC Voltage 400V for 2...

Page 16: ...within a year and the power up time should be at least above five hours When powered up the voltage must be increased slowly with a voltage regulator to the rated voltage value 2 Installation Site an...

Page 17: ...ce stress may cause damage of parts in the main circuit so as to damage the inverter The inverter should be installed on non combustible materials such as iron plate If several inverters are installed...

Page 18: ...interrupter Use one of anti high harmonic Electromagnetic contactor Note Do not use the electromagnetic contactor as the on off button of power supply for the inverter AC reactor It is recommended to...

Page 19: ...ement of Main circuit Terminals HLPA00D423C HLPA01D523C HLPA0D7543C HLPA02D243C HLPA03D743B HLPA02D223B HLPA03D723B HLPA05D543B HLPA07D543B HLPA001143B HLPA003043B HLPA05D523B HLPA003023B HLPA003743B...

Page 20: ...r for braking resistor P1P Connector for DC reactor When using a DC reactor the jumper shall be removed A05D543B and A07D543B internally jumped P N Connecting terminal of external braking bank E Groun...

Page 21: ...rol Signals DRV Multi Output 1 Optical couple output DC12V 100mA UPF Multi Output 2 Optical couple output FA FB FC Multi Output 3 N O or N C 3A 250VAC 3A 30VDC KA KB Multi Output 4 N O 3A 250VAC 3A 30...

Page 22: ...HLP A Series HLP A Series 17 HLPA00D423C HLPA03D723B HLPA0D7543C HLPA03D743B HLPA05D543B HLPA07D543B FC FA FB EV 12V 100mA...

Page 23: ...HLP A Series HLP A Series 18 HLPA001143B HLPA003043B HLPA05D523B HLPA003023B HLPA003743B HLPA041543B HLPA003723B HLPA009023B EV P24...

Page 24: ...ected to the output terminals of the inverter The main circuit wire must be enough far away from other control equipments When the wiring between the inverter and the motor exceeds 15 meters for 220V...

Page 25: ...PA0D7543C 16 2 5 2 5 1 M4 HLPA01D543C 16 2 5 2 5 1 M4 HLPA02D243C 16 2 5 2 5 1 M4 HLPA03D743B 16 2 5 2 5 1 M4 HLPA05D543B 32 4 4 1 M5 HLPA07D543B 40 6 6 1 M5 HLPA001143B 63 6 6 1 M6 HLPA001543B 63 6 6...

Page 26: ...for signal lines Use the control terminals on the control panel correctly according to your needs 3 Grounding Grounding terminal E Be sure to make correct grounding 220V class The third grounding meth...

Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...

Page 28: ...of the Digital Operator Note The inverter of the hardware version C can use the panel OP AC01 the inverter of the hardware version B can use the panel OP AB01 or OP AB02 The panel OP AB01 and OP AB02...

Page 29: ...W 380V OP AC01 HLPA02D243C 2 2KW 380V OP AC01 HLPA03D743B 3 7KW 380V OP AB01 HLPA05D543B HLPA041543B 5 5KW 380V 415KW 380V OP AB02 4 Description of Indicator Lamp Status 1 Description of Indicator Lam...

Page 30: ...g Display the function of CD000 ENTER 000 00 FWD Hz Display the content of CD000 ENTER PROG 50 00 END CD001 50 00 flash FWD Hz FWD Hz Change the content of CD000 Confirm changed value Display END CD00...

Page 31: ...n previous to the power breakdown after its self detection Procedures Display Indicator Lamp Explanation DISP 50 00 FWD Hz Switch to main screen display running frequency F R 50 00 00 00 50 00 REV Hz...

Page 32: ...lt at outputs 2 Commissioning Methods The procedure of the operator is factory set up for the control mode of HLP series The commissioning can be carried out through the digital operator Generally the...

Page 33: ...re the factory setting No other function 00 CD012 Accel Time 1 0 1 6500 0S CD013 Decel Time 1 0 1 6500 0S CD014 Accel Time 2 0 1 6500 0S CD015 Decel Time 2 0 1 6500 0S CD016 Accel Time 3 0 1 6500 0S C...

Page 34: ...cy 3 0 00 400 00 Hz 0 00 CD047 Skip Frequency Range 0 10 10 00 Hz 0 50 CD048 Timer 1 time 0 1 10 0S 0 1 CD049 Timer 2 time 1 100S 1 Input and Output Terminals CD050 Multi input 1 FOR 0 Invalid 1 Run 2...

Page 35: ...20 4 20mA disconnected 21 24 Reserved 25 Auxiliary Pump 1 26 Auxiliary Pump 2 27 Drawing reach 28 PID lower limit alarm 29 PID upper limit alarm 30 Fan act 31 Reserved 32 Braking resistor act 01 CD05...

Page 36: ...speed 3 Disturbance 4 Internal control multi speed 5 Drawing 0 CD077 AutoPLC 0 Stop after running for one cycle 1 Cycling run 2 Auto stop after running for one cycle STOP for intervention 3 Auto Run...

Page 37: ...116 Lasting Time of Stopping Voltage Level 1 250S 30 CD117 Wakeup Level 1 150 80 CD118 Sleep Frequency 0 00 400 00Hz 20 00 CD119 Lasting Time of Sleep Frequency 1 250S 20 Parameters of Protection Func...

Page 38: ...art 0 0 25 0S 0 0 CD142 DC Braking time at stop 0 0 25 0S 0 0 CD143 Frequency track time 0 0 20 0S 5 0 CD144 Current level for frequency track 0 200 150 CD145 Restart after instantaneous Stop 0 Invali...

Page 39: ...er Set according to the model CD170 Rated Current of Inverter Set according to the model CD171 Software Version CD172 Fault Record 1 Note means no fault record CD173 Fault Record 2 CD174 Fault Record...

Page 40: ...relatively far away from the inverter this set value can be increased properly CD002 Base Frequency Set Range 0 01 400 00 Hz Unit 0 01Hz Factory Setting 50 00 This parameter must be set according to...

Page 41: ...A0D7523C 14 0 7 8 8 9 A001543B 19 9 5 20 20 5 A01D523C 14 0 7 10 10 8 A18D543B 18 9 25 25 5 A02D223B 13 0 6 5 10 10 8 A002243B 18 9 25 25 5 A03D723B 13 0 6 5 15 15 7 A003043B 17 8 5 30 30 4 A05D523B 1...

Page 42: ...Ramp Time 2 Ramp Time1x 2 Ramp Time 3 Ramp Time 2 x 2 Ramp Time 4 Ramp Time 3 x 2 Min Voltage Value Intermediate Voltage Value 2 The intermediate frequency is 2 5 for the system of 50Hz The intermedi...

Page 43: ...tting CD017 Decel Time 3 Set Range 0 1 6500 0S Unit 0 1S Factory Setting CD018 Accel Time 4 Set Range 0 1 6500 0S Unit 0 1S Factory Setting CD019 Decel Time 4 Set Range 0 1 6500 0S Unit 0 1S Factory S...

Page 44: ...set to 0 i e DC braking is invalid at start it starts running from the starting frequency When CD141 is set to any non zero value i e DC braking is valid at start itl first performs a DC braking at s...

Page 45: ...he motor For the related parameters refer to CD042 CD140 and CD142 1 Coasting Stop When the inverter receives a STOP command it will immediately stop output and the motor will coast to stop When the c...

Page 46: ...alue 0 1 2 3 4 5 6 7 8 9 10 1 1 12 13 14 15 Carrier Frequency KHz 0 7 1 1 5 2 3 4 5 7 8 9 10 1 1 13 15 1 7 20 As shown in the table above the higher the carrier is the lower the electromagnetic noise...

Page 47: ...nvalid 1 STOP valid This parameter set is only valid when CD033is set to l or 2 When the control mode is set for external terminals or communication control STOP key on the panel can be chosen to be v...

Page 48: ...ry Setting 0 50 When stopping the inverter will decrease its f requency to the stopping frequency and then stop running or start DC braking to stop If CD142 is set to 0 DC braking is invalid at stop a...

Page 49: ...ve diagram CD048 Timer 1 Time Set Range 0 1 10 0S Unit 0 1S Factory Setting 0 1 CD049 Timer 2 Time Set Range 1 100S Unit 1S Factory Setting 1 Timer 1 is a timer of 0 1s 10 0s and Timer 2 is a timer of...

Page 50: ...sed for reset after a fault is removed 1 1 Reserved 12 Over heat of heat sink or motor This contact can be used to detect over heat of the heat sink or motor to protect the motor and inverter 13 Exter...

Page 51: ...achieve the function of AutoPLC clear suspend 32 PID Valid When this contact is closed PID f unction starts PID Function start is only valid during operation Explanation 1 Three multi function termin...

Page 52: ...ple when SPH CD053 is set to 23 and SPM CD054 is set to 24 SPH and SPM are now Ramp Time1 2 SPH SPM Result OFF OFF Ramp Time1 ON OFF Ramp Time 2 OFF ON Ramp Time 3 ON ON Ramp Time 4 4 Function descrip...

Page 53: ...ecrease Note 1 The f unction of UP and DOWN is only valid when the operator is selected for the source of the operating frequency i e CD034 0 2 When the UP terminal is closed the f requency of the inv...

Page 54: ...2 For details refer to CD076 7 Function Description of Counter Note 1 The signal width triggered should not be lower than 2 msec t1 t2 2msec 2 When the counting value is reached the corresponding mult...

Page 55: ...t when the inverter detects over torque 13 Low Voltage Alarm The contact will act when the inverter detects low voltage 14 Single Step End The contact will act and generate one pulse when the inverter...

Page 56: ...it can be connected with a corresponding instrument with the measuring range below 10 to be used for external monitoring 0 0 10V analog output corresponding to output f requency 0 10V corresponds to...

Page 57: ...f unction contacts are changed When output F is higher than uniform F the corresp multioutputs act The uniform F range is uaed as hysteresis LOOP CD064 Counting Value Set Range 0 65500 Unit 1 Factory...

Page 58: ...y Setting 50 00 CD069 Bias Direction at Higher Frequency Set Range 0 1 Unit 1 Factory Setting 0 0 Positive direction 1 Negative direction Bias direction means the instruction of FOR REV rotation comma...

Page 59: ...curve is the extension of the above curve 2V 10V 4 8mA 20mA corresponds to 0Hz 40HZ the signal of 0V 2V 4 4 8mA is invalid It can be used to avoid noice disturbance In harsh environment it is better...

Page 60: ...0 CD055 CD073 UP DOWN Speed Set Range 0 1 Unit 1 Factory Setting 0 0 0 1Hz Minimum UP DOWN speed is 0 1Hz 1 0 01Hz Minimum UP DOWN speed is 0 01Hz Through the changes of this set value the UP DOWN spe...

Page 61: ...CD083 ON OFF ON Multi speed 5 and frequency are determined by CD084 OFF ON ON Multi speed 6 and frequency are determined by CD085 ON ON ON Multi speed 7 and frequency are determined by CD086 Note It i...

Page 62: ...determined by CD086 Running Time is determined by Timer CD087 and CD088 The related parameters CD000 CD080 CD088 4 Internal control Multi speeds Note Main speed and 7 speeds composes 8 speeds The ram...

Page 63: ...i function terminal the drawing action begins In implementation of the drawing action the actual running time is T CD087 10 when the drawing action is finished the inverter will run at the constant se...

Page 64: ...for intervention Note When the command of auto program operation is given the inverter will run with each parameters But it will stop first and then restart at changing of each step and will stop auto...

Page 65: ...o 4 This parameter is set to determine the ramp time values for Step 1 4 of the internal control multi speed The setting method is as follows Determine each Ramp Time in the binary 2 bit mode Bit1 Bit...

Page 66: ...4 CD087 Timer 1 Factory Setting 10 0 CD088 Timer 2 Factory Setting 10 0 CD089 Timer 3 Factory Setting 0 0 CD090 Timer 4 Factory Setting 0 0 CD091 Timer 5 Factory Setting 0 0 CD092 Timer 6 Factory Sett...

Page 67: ...nterlocking time of two auxiliary pumps when switching with each other CD112 Interlocking Time of Auxiliary Pump Set Range 0 1 250 0S Unit 0 1S Factory Setting In the application of water supply with...

Page 68: ...level before entering into sleep mode For details refer to the following description CD116 Lasting Time of Stopping Voltage Level Set Range 1 250S Unit 1S Factory Setting 30 This parameter is set for...

Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...

Page 70: ...prevention valid When the inverter is in deceleration due to the effect of load inertia the motor will produce a return energy to the inverter and cause the DC voltage of the CD120 Over voltage Stall...

Page 71: ...o accelerate CD121 Stall Prevention Level at Ramp up Set Range 0 200 Unit 1 Factory Setting 150 100 current is the rated current of the motor When this parameter is set to 0 the stall prevention funct...

Page 72: ...ction will indicate and the corresponding multi f unction alarm contact will act When it exceeds the set time the inverter will turn to self protection When this parameter is set to 0 the over torque...

Page 73: ...is rising rapidly the current will be higher and the tracking process will be faster When the voltage is rising slowly the current will be lower and the tracking process will be slower In general prac...

Page 74: ...eter is set for the DC braking voltage to the motor at start and stop It can be adjusted for different braking voltage When adjusting the parameter it must be increased slowly from lower value to high...

Page 75: ...t The inverter will trace the frequency from high to low with the set frequency After searching it will continue to accelerate to reach the set frequency CD143 Frequency Track Time Set Range 0 1 20 0S...

Page 76: ...r with the power exceeding the rated voltage will cause increase of the temperature of the motor damage of its insulation and unstable output torque This auto voltage regulation can automatically stab...

Page 77: ...e D value is the more obvious the depression operation will be When D is set to zero this function is invalid CD152 Differential Time D Set Range 0 00 10 00s Unit 0 01s Factory Setting 0 This target v...

Page 78: ...application descriptions in Appendix1 1 Suppress the Over Output a Decrease the differential time D value b Increase the integral time I value 2 Suppress the oscillation a Decrease the differential ti...

Page 79: ...CD160 Communication Addresses Set Range 0 250 Unit 1 Factory Setting 0 CD157 CD159 Reserved 0 4800 b s 1 9600 b s 2 19200 b s 3 38400 b s CD161 Communication Band Rate Set Range 0 3 Unit Factory Sett...

Page 80: ...ta 64H hexadecimal is composed of ASC II byte 64 included 6 36H and 4 34H Byte 0 1 2 3 4 5 6 7 ASCII code 30H 31H 32H 33H 34H 35H 36H 37H Byte 8 9 A B C D E F ASCII code 38H 39H 41H 42H 43H 44H 45H 46...

Page 81: ...s MODBUS 01 250 Address of the corresponding inverters 3 FUNC Function code 8 bit data is composed of two ASC II byte 01 FUNC READ Read the data of function code 02 FUNC WRIT write the data of functio...

Page 82: ...NTR ADDR 0 for broadcast it write to all inverter but no reply ADDR 0 reply and return CNTR 7 6 5 4 3 2 1 0 jogr jogf jog r f stop rev for run When the setting is correct it will return to present con...

Page 83: ...42H 38H 33H 37H 0DH 0AH 3 2 RTU Mode Quiet ADDR FUNC LEN D n 1 D 0 CRC Quiet 50ms 50ms 1 Quiet the time of no data is more than 50 ms 2 ADDR Communication address 8 bit data 3 FUNC Function code 8 bi...

Page 84: ...igned char data the point of data buffer Unsigned char length number of data buffer This f unction will send back the CRC value with unsigned integer format Unsigned int crc_chk unsigned char data uns...

Page 85: ...w output frequency set frequency output current and output revolution through the switch key If it is necessary to view and monitor other items they can be set through CD167 and CD168 Factory setting...

Page 86: ...MODBUS Communication Protocol It is factory setting It can be observed but not set CD179 Manufacture date Factory Setting Week Month Year CD180 Serial No Factory Setting CD181 Reserved CD183 CD250 Res...

Page 87: ...fter the installation 2 Periodical Inspection and Maintenance items Check whether the power supply voltage conforms to the rated voltage of the inverter Pay special attention to that whether there is...

Page 88: ...be increased 4 Decrease the torque and increase the set value E OC n Over current at constant speed 1 Check whether the motor has got short circuit and whether the insulation of the output wires is g...

Page 89: ...ormal 3 Check whether there is enough space for ventilation and good air convection E OL A E OL n E OL d Inverter overload 150 Per minute 1 Check whether the capacity of the inverter is lower Otherwis...

Page 90: ...ES Emergency Stop In Emergency Stop 20 4 20mA wire broken Join the broken wires Pr Setting error Correct the setting DCb DC braking status In DC braking Note 1 Fault Code Form as follows Status Alarm...

Page 91: ...The communication of the digital operator is abnormal Take out the operator after power off and then mount it again for a trial 3 The motor cannot rotate reverse Reverse rotation is disabled 4 The mot...

Page 92: ...ield it 6 Make separate wiring for the main circuit wires and control wires 8 When the fan starts the inverter detected an over current stall 1 At start the fan rotates idly Please set it for DC braki...

Page 93: ...verter and prevent the shock of surge voltage Braking resistor braking unit Consume the regenerating energy of the motor and shorten the ramp down time 1 Leakage switch There is earth static capacity...

Page 94: ...obvious effect of decreasing high order harmonic at input If it is necessary to install a DC reactor please contact the local distributor 2 Disposition 1 DC Reactors Disposition DC Reactor Model Match...

Page 95: ...rove the power factor of the inverter 2 AC Reactors Disposition AC Reactor Model Matched Power W Rated Current A Inductance mH HKSG2 24 1 1 24 0 52 HKSG2 34 15 34 0 397 HKSG2 38 1 8 5 38 0 352 HKSG2 5...

Page 96: ...5 0 75 HLPA01D523C 300 100 125 1 5 HLPA02D223C 300 70 125 2 2 HLPA0D7543C 80 750 125 0 75 HLPA01D543C 300 400 125 1 5 HLPA02D243C 300 250 125 2 2 HLPA03D743B 400 150 125 3 7 HLPA05D543B 500 100 125 5...

Page 97: ...uick brake a braking unit must be added Note 1 Please select the resistor value and operating f requency given by our company 2 If it causes any damage to the inverter and other devices due to the use...

Page 98: ...CD000 30 CD080 27 CD086 0 5 CD087 10 CD088 10 2 Drawing Function Parameter setting CD076 5 CD000 25 CD080 50 CD081 30 CD087 720 CD052 29 CD033 1 Note When triggered by external multi f unction termina...

Page 99: ...ontrol 8 speed run will stop after running for one cycle Parameter setting CD076 4 CD000 30 CD080 50 CD081 30 CD082 20 CD083 40 CD084 10 CD085 35 CD086 15 CD078 36 CD077 0 CD012 5 CD013 5 CD033 1 CD07...

Page 100: ...For example For FInverter1 FInverter2 FInverter3 1 2 3 the parameters of CD068 can be adjusted Frequency1 CD068 50 Frequency 2 CD068 100 Frequency 3 CD068 150 In case of the analog of 10V the corresp...

Page 101: ...r Frequency Variable Frequency Note K is a switch for power frequency variable frequency K1 is a start button and K2 is a stop button for power frequency The stopping mode is set for coasting stop K3...

Page 102: ...9 CD150 CD15 1 CD152 CD153 50 CD154 0 CD155 60 CD156 40 CD033 1 Note CD150 CD151 and CD152 should be set according to the actual conditions For general water supply with constant pressure CD150 80 100...

Page 103: ...stor in parallel for correction Output resistance values vary with different manufacturers of resistance transmission pressure gauge After conversion the levels of current signal are different The use...

Page 104: ...hen it is required to stop due to fault and process or other reasons K1will be opened And the inverter will stop output and suspend counting time After the fault is removed K1 will be closed and the i...

Page 105: ...Appendix 2 Appearance and Installation Dimensions Inverter Model Appearance and Installation Dimensions HLPA00D423C HLPA0D7523C HLPA01D523C HLPA0D7543C HLPA01D543C HLPA02D243C Unit mm HLPA02D223B HLP...

Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...

Page 107: ...HLP A Series HLP A Series 102 HLPA001 123B HLPA005523B HLPA001 143B HLPA005543B Unit mm HLPA007523B HLPA009023B HLPA007543B HLPA016043B Unit mm...

Page 108: ...HLPA00D423C 1 16 125 161 1 70 141 5 HLPA0D7523C HLPA01D523C HLPA0D7543C HLPA01D543C HLPA02D243C HLPA02D223B HLPA03D723B HLPA03D743B 128 140 238 250 157 5 HLPA05D523B HLPA07D523B 130 208 325 340 199 7...

Page 109: ...800 350 16 16 HLPA004523B HLPA009043B 300 450 828 860 350 16 16 HLPA005523B 500 650 868 900 400 16 16 HLPA007523B HLPA009023B HLPA01 1043B HLPA013243B HLPA016043B 560 650 868 900 400 16 16 HLPA013243B...

Page 110: ...HLP A Series HLP A Series 105 Appendix 3 Appearance and Installation Dimensions Type Appearance and Installation Dimensions OP AB01 OP AC01 Unit mm OP AB02 Unit mm...

Page 111: ...cted separately to earth and must not be connected to zero line U V W should be connected to the motor and the earth wire must be correctly separately connected to earth The three ends of potentiomete...

Page 112: ...control CD034 1 External potentiometer control CD050 1 FOR terminal is set to RUN Close RUN Open STOP Finally CD010 1 Parameter Lock i e lock the parameters When it needs to be reset first set CD010 t...

Page 113: ...CD109 Reserved CD009 Frequency Lower Limit 0 00 CD1 10 Number of Auxiliary Pump 0 CD010 Parameter Lock 0 CD1 1 1 Continuous Operating Time of Aux Pump 60 CD01 1 Parameter Reset 00 CD1 12 Interlocking...

Page 114: ...age CD039 S Curve Time 0 0 CD13 1 Rated Motor Current CD040 Up down 0 01 CD132 Motor Pole Number 04 CD041Starting Frequency 0 50 CD133 Rated Motor Revolution 1440 CD042Stopping Frequency 0 50 CD134 Mo...

Page 115: ...resses 00 CD064Counting value set 00 CD161 Communication Baud Rate 1 CD065 Analog Input 0 CD162 Communication Data Method 0 CD066 Lower Analog Frequency 0 00 CD163 CD166 Reserved CD067 Bias Direction...

Page 116: ...Factory Setting User s Par CD080 Frequency 2 15 00 CD180 Serial No CD081 Frequency 3 20 00 CD181 Reserved CD082 Frequency 4 25 00 CD182 Communication Protocol Select 0 CD083 Frequency 5 30 00 CD183 C...

Page 117: ......