CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
7-13
7
•
Message
: "Unauthorized firmware attempt"
•
Latched target message
: No.
•
Description of problem
: A firmware upgrade operation was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the relay and try again.
•
Message
: "Unauthorized setting write"
•
Latched target message
: No.
•
Description of problem
: A setting write was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the settings and try again.
•
Message
: "An attempt to contact the Radius server has failed"
•
Latched target message
: No.
•
Description of problem
: The RADIUS authentication server is unavailable.
•
What to do
: Verify network connectivity and try again.
•
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
•
How often the test is performed: On relay power-up and afterwards once every 24 hours.
•
What to do: Contact the factory.
•
Description of problem
: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
•
What to do
: Update firmware to either of these builds.
•
Description of problem: In version 7.41, if more breaker elements are enabled than the number of installed DSP
modules, the excess elements are not functional and can trigger self-test error "Module Failure 33." In release 7.42 and
later, the firmware does not allow enabling more breaker restrike elements than the number of installed DPS modules,
and upon attempt, the relay displays a minor self-test message as follows:
"BKR RESTRIKE ELMENT:
MAXIMUM EXCEEDED"
•
What to do: Upgrade to version 7.42 or later.
7.2.2.4 HardFiber major self-test error messages
In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95
Plus
, see that product’s instruction manual.
FIRMWARE LOCK
SETTING LOCK
SERVER UNAVAILABLE
DOS PARTITION ALARM:
SELF-TEST ERROR
PROTOTYPE FIRMWARE:
Self Test Error
BKR RESTRIKE ELMENT:
MAXIMUM EXCEEDED