CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-363
5
BREAKER RESTRIKE 1 HF DETECT
— Enables/disables high-frequency (HF) pattern detection when breaker restrike occurs.
High-frequency pattern is typical for capacitor bank, cables, and long transmission lines applications.
BRK RSTR 1 BRK OPEN
— Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic “1” when
the breaker is open. It is important to assign either 52 contact with this setting or breaker close command with
BRK RSTR 1
CLS CMD
setting to give clear indication to the relay about breaker status.
BRK RSTR 1 OPEN CMD
— Assigns a FlexLogic operand indicating a breaker open command. It must be logic “1” when the
breaker is opened, either manually or from protection logic.
BRK RSTR 1 CLS CMD
— Assigns a FlexLogic operand indicating a breaker close command. It must be logic “1” when the
breaker is closed.
Figure 5-207: Breaker restrike logic
5.8.11.5 Continuous monitor
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
CONTINUOUS MONITOR
CONTINOUS MONITOR
CONT MONITOR
FUNCTION: Disabled
Range: Disabled, Enabled
CONT MONITOR I-OP:
Off
Range: FlexLogic operand
Any Current Element(s) OP
CONT MONITOR I-SUPV:
Off
Range: FlexLogic operand.
To supervise current logic, use 50DD OP.
CONT MONITOR V-OP:
Off
Range: FlexLogic operand
Any Voltage Element(s) OP
CONT MONITOR V-SUPV:
Off
Range: FlexLogic operand. To supervise voltage
logic, use VT FUSE FAIL OP.
CONT MONITOR
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
CONT MONITOR
EVENTS: Disabled
Range: Disabled, Enabled