CHAPTER 6: ACTUAL VALUES
STATUS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
6-9
6
6.3.13 Selector switches
ACTUAL VALUES
STATUS
SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.3.14 Flex states
ACTUAL VALUES
STATUS
FLEX STATES
There are 256 FlexState
TM
bits available. The second line value indicates the state of the given FlexState bit.
6.3.15 Ethernet
ACTUAL VALUES
STATUS
ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
6.3.16 Real time clock synchronizing
ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
Range: Current Position / 7
SELECTOR SWITCH 2
POSITION: 0/7
Range: Current Position / 7
FLEX STATES
PARAM 1: Off
Off
Range: On, Off
PARAM 256: Off
Off
Range: On, Off
ETHERNET
ETHERNET PRI LINK
STATUS: Fail
Range: Fail, OK
ETHERNET SEC LINK
STATUS: Fail
Range: Fail, OK
ETHERNET TER LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC SYNC SOURCE:
None
Range: see below
GRANDMASTER ID:
0X0000000000000000
Range: any 8 octet value
ACCURACY:
999999999 ns
Range: 0 to 999,999,999 ns
PORT 1 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 2 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 3 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PTP - IRIG-B DELTA:
500000000 ns
Range: -500,000,000 to +500,000,000 ns