5-292
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-160: Negative-sequence directional OC1 logic
5.7.13 Breaker failure (ANSI 50BF)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
BREAKER FAILURE
BREAKER FAILURE 1(4)
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
BF1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BF1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
BF1 USE AMP SUPV:
Yes
Range: Yes, No
BF1 USE SEAL-IN:
Yes
Range: Yes, No
BF1 3-POLE INITIATE:
Off
Range: FlexLogic operand
BF1 BLOCK:
Off
Range: FlexLogic operand
BF1 RETRIP PICKUP
DELAY: 0.033 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 PH AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 N AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 USE TIMER 1:
Yes
Range: Yes, No