CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-293
5
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 USE TIMER 2:
Yes
Range: Yes, No
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 USE TIMER 3:
Yes
Range: Yes, No
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 BKR POS1
φ
A/3P:
Off
Range: FlexLogic operand
BF1 BKR POS2
φ
A/3P:
Off
Range: FlexLogic operand
BF1 BREAKER TEST ON:
Off
Range: FlexLogic operand
BF1 PH AMP HISET
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 N AMP HISET
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 PH AMP LOSET
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 N AMP LOSET
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 LOSET TIME
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 TRIP DROPOUT
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 TARGET:
Self-Reset
Range: Self-reset, Latched, Disabled
BF1 EVENTS:
Disabled
Range: Disabled, Enabled
BF1 PH A INITIATE:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 PH B INITIATE:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 PH C INITIATE:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 BKR POS1
φ
B:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 BKR POS1
φ
C:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 BKR POS2
φ
B:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes
BF1 BKR POS2
φ
C:
Off
Range: FlexLogic operand
Valid only for 1-Pole breaker failure schemes