5-394
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
DCUB BLOCK:
Off
Range: FlexLogic operand
DCUB PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled, Custom
DCUB ECHO COND:
Off
Range: FlexLogic operand
GND DIR O/C FWD:
Off
Range: FlexLogic operand
GND DIR O/C REV:
Off
Range: FlexLogic operand
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0 to 65.535 s in steps of 0.001
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0 to 65.535 s in steps of 0.001
ECHO DURATION:
0.100 s
Range: 0 to 65.535 s in steps of 0.001
ECHO LOCKOUT:
0.250 s
Range: 0 to 65.535 s in steps of 0.001
LINE END OPEN PICKUP
DELAY: 0.050 s
Range: 0 to 65.535 s in steps of 0.001
DCUB LOG PICKUP
DELAY: 0.008 s
Range: 0 to 65.535 s in steps of 0.001
GUARD HEALTHY RESET
DELAY: 0.015 s
Range: 0 to 65.535 s in steps of 0.001
DCUB LOG TRIP
WINDOW: 0.150 s
Range: 0 to 65.535 s in steps of 0.001
DCUB SEAL-IN
DELAY: 0.010 s
Range: 0 to 65.535 s in steps of 0.001
DCUB NO OF COMM
BITS: 1
Range: 1, 2, or 4
DCUB RX1:
Off
Range: FlexLogic operand
DCUB LOG1:
Off
Range: FlexLogic operand
DCUB RX2:
Off
Range: FlexLogic operand
DCUB LOG2:
Off
Range: FlexLogic operand
DCUB RX3:
Off
Range: FlexLogic operand
DCUB LOG3:
Off
Range: FlexLogic operand
DCUB RX4:
Off
Range: FlexLogic operand
DCUB LOG4:
Off
Range: FlexLogic operand
DCUB SCHEME TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled