10-44
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SINGLE-POLE TRIPPING
CHAPTER 10: THEORY OF OPERATION
10
Table 10-21: Blocking scheme transmit codes for two-bit channels
Table 10-22: Unblocking scheme transmit codes for two-bit channels
The action output is generated per the following tables.
Table 10-23: Permissive scheme trip table for two-bit channels
Table 10-24: Blocking scheme trip table for two-bit channels
Phase selector
determination of fault
type
Bit pattern transmitted
FlexLogic operands asserted
TX1
TX2
TX1 STOP
TX2 STOP
AG, BC, BCG
0
1
1
0
BG, CA, CAG
1
0
0
1
CG, AB, ABG, 3P
0
0
1
1
CG, AB, ABG, 3P,
Unrecognized
0
0
1
1
Phase selector determination of
fault type
Bit pattern transmitted
TX1
TX2
AG, BC, BCG
1
0
BG, CA, CAG
0
1
CG, AB, ABG, 3P, Unrecognized
1
1
Remote data
Local data
Bit pattern received
Remote determination of fault
type
Local determination of fault
type
Trip output
RX1
RX2
1
0
AG, BC, BCG
AG, AB, ABG CA, CAG, 3P
Trip Phase A
0
1
BG, CA, CAG
AG
1
1
CG, AB, ABG, 3P, Unrecognized
AG
0
1
BG, CA, CAG
BG, AB, ABG, BC, BCG, 3P
Trip Phase B
1
1
CG, AB, ABG, 3P, Unrecognized
BG
1
0
AG, BC, BCG
BG
1
1
CG, AB, ABG, 3P, Unrecognized
CG, BC, BCG, CA, CAG
Trip Phase C
1
0
AG, BC, BCG
CG
0
1
BG, CA, CAG
CG
1
1
CG, AB, ABG, 3P, Unrecognized
AB, ABG, 3P, Unrecognized
Trip Three Phases
1
0
AG, BC, BCG
BC, BCG, Unrecognized
0
1
BG, CA, CAG
CA, CAG, Unrecognized
Remote data
Local data
Bit pattern received
Remote determination of fault
type
Local determination of fault
type
Trip output
RX1
RX2
0
1
AG, BC, BCG
AG, AB, ABG CA, CAG, 3P
DIR BLOCK TRIP A
1
0
BG, CA, CAG
AG
0
0
CG, AB, ABG, 3P, Unrecognized
AG
1
0
BG, CA, CAG
BG, AB, ABG, BC, BCG, 3P
DIR BLOCK TRIP B
0
0
CG, AB, ABG, 3P, Unrecognized
BG
0
1
AG, BC, BCG
BG
0
0
CG, AB, ABG, 3P, Unrecognized
CG, BC, BCG, CA, CAG
DIR BLOCK TRIP C
0
1
AG, BC, BCG
CG
1
0
BG, CA, CAG
CG