L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
5.8.12 Pilot schemes
5.8.12.1 Menu
SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
This menu is for selection and configuration of protection signaling schemes. All schemes are available for single-pole
tripping applications and can be used with one, two, or four-bit communications channels. Choices of communications
channel include Remote Inputs/Outputs and telecommunications interfaces.
For more information, see the Application of Settings chapter.
5.8.12.2 Direct under-reaching transfer trip (DUTT)
SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
DUTT SCHEME
PILOT SCHEMES
DUTT SCHEME
See below
PUTT SCHEME
POTT SCHEME
POTT1 SCHEME
HYBRID POTT SCHEME
BLOCKING SCHEME
BLOCKING1 SCHEME
DCUB SCHEME
DUTT SCHEME
DUTT SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
DUTT SCHEME BLOCK:
Off
Range: FlexLogic operand
DUTT SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
DUTT NO OF COMM
BITS: 1
Range: 1, 2, or 4
DUTT RX1:
Off
Range: FlexLogic operand
DUTT RX2:
Off
Range: FlexLogic operand
DUTT RX3:
Off
Range: FlexLogic operand
DUTT RX4:
Off
Range: FlexLogic operand
DUTT SCHEME TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
DUTT SCHEME EVENT:
Disabled
Range: Disabled, Enabled