5-142
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
Figure 5-63: Example of use of sources
5.5.4 87L power system
5.5.4.1 Menu
SETTINGS
SYSTEM SETUP
87L POWER SYSTEM
Y LV
D HV
AUX
SRC 1
SRC 2
SRC 3
Phase CT
M1
F1+F5
None
Ground CT
M1
None
None
Phase VT
M5
None
None
Aux VT
None
None
U1
87L POWER SYSTEM
NUMBER OF TERMINALS:
2
Range: 2, 3
NUMBER OF CHANNELS:
1
Range: 1, 2
CHARGING CURRENT
COMPENSATN: Disabled
Range: Disabled, Enabled
POS SEQ CAPACITIVE
REACTANCE: 0.100 k
Ω
Range: 0.100 to 65.535 k
Ω
in steps of 0.001