8-28
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PHASE DISTANCE THROUGH POWER TRANSFORMERS
CHAPTER 8: APPLICATION OF SETTINGS
8
The Zone 1 settings are:
Eq. 8-20
PHS DIST Z1 REACH
: "0.80"
PHS DIST Z1 RCA
: "85"
PHS DIST Z1 XMFR VOL CONNECTION
: "None"
PHS DIST Z1 XMFR CUR CONNECTION
: "Dy1"
The Zone 4 settings are:
Eq. 8-21
PHS DIST Z4 REACH
: "2.60"
PHS DIST Z4 RCA
: "89"
PHS DIST Z4 XMFR VOL CONNECTION
: "Yd11"
PHS DIST Z4 XMFR CUR CONNECTION
:
"None"