L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-172: Auxiliary overvoltage logic
5.7.14.7 Volts per hertz (ANSI 24, IEC PVPH)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
VOLTS/HZ 1(2)
The per-unit volts-per-hertz (V/Hz) value is calculated using the maximum of the three-phase voltage inputs or the auxiliary
voltage channel Vx input, if the source is not configured with phase voltages. To use the V/Hz element with auxiliary
voltage, set
SYSTEM SETUP
SIGNAL SOURCES
SOURCE 1(6)
SOURCE 1(6) PHASE VT
to “None” and
SOURCE 1(6) AUX VT
to
the corresponding voltage input bank. If there is no voltage on the relay terminals in either case, the per-unit V/Hz value is
automatically set to “0”. The per unit value is established as per voltage and nominal frequency power system settings as
follows:
1.
If the phase voltage inputs defined in the source menu are used for V/Hz operation, then “1 pu” is the selected
SYSTEM
SETUP
AC INPUTS
VOLTAGE BANK N
PHASE VT N SECONDARY
setting, divided by the divided by the
SYSTEM SETUP
POWER SYSTEM
NOMINAL FREQUENCY
setting.
VOLTS/HZ 1
VOLTS/HZ 1 FUNCTION:
Disabled
Range: Disabled, Enabled
VOLTS/HZ 1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
VOLTS/HZ 1 VOLTAGE
MODE: Phase-ground
Range: Phase-ground, Phase-phase
VOLTS/HZ 1 PICKUP:
1.00 pu
Range: 0.80 to 4.00 pu in steps of 0.01
VOLTS/HZ 1 CURVE:
Definite Time
Range: Definite Time, Inverse A, Inverse B, Inverse C,
FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve D
VOLTS/HZ 1 TD
MULTIPLIER: 1.00
Range: 0.05 to 600.00 in steps of 0.01
VOLTS/HZ 1
T-RESET: 1.0 s
Range: 0.0 to 1000.0 s in steps of 0.1
VOLTS/HZ 1 BLOCK:
Off
Range: FlexLogic operand
VOLTS/HZ 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
VOLTS/HZ 1 EVENTS:
Disabled
Range: Disabled, Enabled
For the L90, this feature is optional and requires software option 24 or 83. Check the order code of your device.