5-370
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-212: Open pole detector logic (Sheet 2 of 2)
5.8.11.9 Thermal overload protection (ANSI 49)
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
THERMAL OVERLOAD PROTECTION
THERMAL PROTECTION 1(2)
THERMAL
PROTECTION 1
THERMAL PROTECTION 1
FUNCTION: Disabled
Range: Disabled, Enabled
THERMAL PROTECTION 1
SOURCE: SRC1
Range: SRC 1, SRC 2, SRC 3, SRC 4
THERMAL PROTECTION 1
BASE CURR: 0.80 pu
Range: 0.20 to 3.00 pu in steps of 0.01
THERMAL PROTECTION 1
k FACTOR: 1.10
Range: 1.00 to 1.20 in steps of 0.05
THERM PROT 1 TRIP
TIME CONST: 45 min
Range: 0 to 1000 min. in steps of 1
THERM PROT 1 RESET
TIME CONST: 45 min
Range: 0 to 1000 min. in steps of 1
THERM PROT 1 MINIM
RESET TIME: 20 min
Range: 0 to 1000 min. in steps of 1
THERM PROT 1 RESET:
Off
Range: FlexLogic operand
THERM PROT 1 BLOCK:
Off
Range: FlexLogic operand
THERMAL PROTECTION 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
THERMAL PROTECTION 1
EVENTS: Disabled
Range: Disabled, Enabled