GE Multilin
G60 Generator Protection System
E-5
APPENDIX E
E.1 DEVICE PROFILE DOCUMENT
E
20
cont’d
2
16-Bit Binary Counter
1
(read)
7
(freeze)
8
(freeze noack)
9
(freeze clear)
10
(frz. cl. noack)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
5
32-Bit Binary Counter without Flag
1
(read)
7
(freeze)
8
(freeze noack)
9
(freeze clear)
10
(frz. cl. noack)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
6
16-Bit Binary Counter without Flag
1
(read)
7
(freeze)
8
(freeze noack)
9
(freeze clear)
10
(frz. cl. noack)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
21
0
Frozen Counter
(Variation 0 is used to request default
variation)
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
1
32-Bit Frozen Counter
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
2
16-Bit Frozen Counter
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
9
32-Bit Frozen Counter without Flag
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
10
16-Bit Frozen Counter without Flag
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
22
0
Counter Change Event (Variation 0 is used
to request default variation)
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
1
32-Bit Counter Change Event
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
2
16-Bit Counter Change Event
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
5
32-Bit Counter Change Event with Time
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
6
16-Bit Counter Change Event with Time
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
23
0
Frozen Counter Event (Variation 0 is used
to request default variation)
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
1
32-Bit Frozen Counter Event
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
2
16-Bit Frozen Counter Event
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
129
(response)
130
(unsol. resp.)
17, 28
(index)
Table E–2: IMPLEMENTATION TABLE (Sheet 2 of 4)
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
Note 1:
A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the
Communications
section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3:
Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...