GE Multilin
G60 Generator Protection System
B-19
APPENDIX B
B.4 MEMORY MAPPING
B
40C2
DNP client address 3
0 to 4294967295
---
1
F003
0
40C4
DNP client address 4
0 to 4294967295
---
1
F003
0
40C6
DNP client address 5
0 to 4294967295
---
1
F003
0
40C8
DNP number of paired binary output control points
0 to 32
---
1
F001
0
40C9
DNP TCP connection timeout
10 to 65535
---
1
F001
120
40CA
Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP port number for the IEC 60870-5-104 protocol
1 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 protocol function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 protocol common address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 protocol cyclic data transmit period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 current default threshold
0 to 65535
---
1
F001
30000
40E6
IEC 60870-5-104 voltage default threshold
0 to 65535
---
1
F001
30000
40E8
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EA
IEC 60870-5-104 energy default threshold
0 to 65535
---
1
F001
30000
40EC
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EE
IEC 60870-5-104 other default threshold
0 to 65535
---
1
F001
30000
40F0
IEC 60870-5-104 client address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 redundancy port
0 to 1
---
1
F126
0 (No)
4005
Reserved (59 items)
0 to 1
---
1
F001
0
4140
DNP object 1 default variation
1 to 2
---
1
F001
2
4141
DNP object 2 default variation
1 to 3
---
1
F001
2
4142
DNP object 20 default variation
0 to 3
---
1
F523
0 (1)
4143
DNP object 21 default variation
0 to 3
---
1
F524
0 (1)
4144
DNP object 22 default variation
0 to 3
---
1
F523
0 (1)
4145
DNP object 23 default variation
0 to 3
---
1
F523
0 (1)
4146
DNP object 30 default variation
1 to 5
---
1
F001
1
4147
DNP object 32 default variation
0 to 5
---
1
F525
0 (1)
Ethernet switch (Read/Write Setting)
4148
Ethernet switch IP address
0 to 4294967295
---
1
F003
3232235778
414A
Ethernet switch Modbus IP port number
1 to 65535
---
1
F001
502
414B
Ethernet switch Port 1 Events
0 to 1
---
1
F102
0 (Disabled)
414C
Ethernet switch Port 2 Events
0 to 1
---
1
F102
0 (Disabled)
414D
Ethernet switch Port 3 Events
0 to 1
---
1
F102
0 (Disabled)
414E
Ethernet switch Port 4 Events
0 to 1
---
1
F102
0 (Disabled)
414F
Ethernet switch Port 5 Events
0 to 1
---
1
F102
0 (Disabled)
4150
Ethernet switch Port 6 Events
0 to 1
---
1
F102
0 (Disabled)
Ethernet switch (Read Only Actual Values)
4151
Ethernet switch MAC address
---
---
1
F072
0
4154
Ethernet switch Port 1 Status
0 to 2
---
1
F134
0 (Fail)
4155
Ethernet switch Port 2 Status
0 to 2
---
1
F134
0 (Fail)
4156
Ethernet switch Port 3 Status
0 to 2
---
1
F134
0 (Fail)
4157
Ethernet switch Port 4 Status
0 to 2
---
1
F134
0 (Fail)
4158
Ethernet switch Port 5 Status
0 to 2
---
1
F134
0 (Fail)
4159
Ethernet switch Port 6 Status
0 to 2
---
1
F134
0 (Fail)
415A
Switch Firmware Version
0.00 to 99.99
---
0.01
F001
0
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) server IP address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP port number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (continuous)
Table B–9: MODBUS MEMORY MAP (Sheet 12 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...