5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.4 POWER SWING DETECT
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...