GE Multilin
G60 Generator Protection System
5-183
5 SETTINGS
5.6 GROUPED ELEMENTS
5
e) NEGATIVE-SEQUENCE OVERVOLTAGE
(ANSI 59_2)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
VOLTAGE ELEMENTS
ÖØ
NEG SEQ OV1(3)
There are three negative-sequence overvoltage elements available.
The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed
phase sequence of voltage, or a non-symmetrical system voltage condition.
Figure 5–101: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC
NEG SEQ OV1
NEG SEQ OV1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
NEG SEQ OV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
NEG SEQ OV1 PICKUP:
0.300 pu
Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
NEG SEQ OV1 PICKUP
DELAY: 0.50
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
NEG SEQ OV1 RESET
DELAY: 0.50
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
NEG SEQ OV1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
NEG SEQ OV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
NEG SEQ OV1 EVENTS:
Disabled
Range: Disabled, Enabled
SETTING
SETTINGS
FLEXLOGIC OPERANDS
SETTING
SETTING
NEG SEQ OV1
FUNCTION:
NEG SEQ OV1 RESET
DELAY:
NEG SEQ OV1 PICKUP
DELAY:
NEG SEQ OV1 PKP
NEG SEQ OV1 DPO
NEG SEQ OV1 OP
NEG SEQ OV1 BLOCK:
Disabled = 0
Off = 0
Enabled = 1
NEG SEQ OV1 SIGNAL
SOURCE:
Wye VT
Delta VT
V_2
827839A3.CDR
AND
SETTING
NEG SEQ OV1 PICKUP:
V_2 or 3 × V_2
PKP
≥
RUN
t
t
PKP
RST
3 × V_2
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...