B-22
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4505
Auxiliary VT 1 Secondary
50 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
---
---
---
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency And Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
4604
Reverse Phase Rotation
0 to 65535
---
1
F300
0
Breaker control (read/write settings)
4700
Breaker 1 function
0 to 1
---
1
F102
0 (Disabled)
4701
Breaker 1 name
---
---
---
F206
“Bkr 1"
4704
Breaker 1 mode
0 to 1
---
1
F157
0 (3-Pole)
4705
Breaker 1 open
0 to 65535
---
1
F300
0
4706
Breaker 1 close
0 to 65535
---
1
F300
0
4707
Breaker 1 phase A / three-pole closed
0 to 65535
---
1
F300
0
4708
Breaker 1 phase B closed
0 to 65535
---
1
F300
0
4709
Breaker 1 phase C closed
0 to 65535
---
1
F300
0
470A
Breaker 1 external alarm
0 to 65535
---
1
F300
0
470B
Breaker 1 alarm delay
0 to 1000000
s
0.001
F003
0
470D
Breaker 1 pushbutton control
0 to 1
---
1
F102
0 (Disabled)
470E
Breaker 1 manual close recall time
0 to 1000000
s
0.001
F003
0
4710
Breaker 1 out of service
0 to 65535
---
1
F300
0
4711
Breaker 1 block open
0 to 65535
---
1
F300
0
4712
Breaker 1 block close
0 to 65535
---
1
F300
0
4713
Breaker 1 phase A / three-pole opened
0 to 65535
---
1
F300
0
4714
Breaker 1 phase B opened
0 to 65535
---
1
F300
0
4715
Breaker 1 phase C opened
0 to 65535
---
1
F300
0
4716
Breaker 1 operate time
0 to 2
s
0.001
F001
70
4717
Breaker 1 events
0 to 1
---
1
F102
0 (Disabled)
4718
Reserved
---
---
---
---
---
4719
...Repeated for breaker 2
4732
...Repeated for breaker 3
474B
...Repeated for breaker 4
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
0 to 1
---
1
F102
0 (Disabled)
47A1
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
47A2
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
47A3
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
47A5
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
47A6
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
47A7
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...