B-42
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
9A17
FlexElement™ 12 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A19
FlexElement™ 13 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1B
FlexElement™ 14 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1D
FlexElement™ 15 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1F
FlexElement™ 16 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00
Teleprotection Function
0 to 1
---
1
F102
0 (Disabled)
9B01
Teleprotection Number of Terminals
2 to 3
---
1
F001
2
9B02
Teleprotection Number of Channels
1 to 2
---
1
F001
1
9B03
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9B04
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9B05
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9B06
Reserved (10 items)
0 to 1
---
---
F001
0
9B10
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B30
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B50
Teleprotection Output 1-n Operand (16 items)
0 to 65535
---
1
F300
0
9B70
Teleprotection Output 2-n Operand (16 items)
0 to 65535
---
1
F300
0
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90
Teleprotection Clear Lost Packets
0 to 1
---
1
F126
0 (No)
Teleprotection Channel Tests (Read Only)
9B91
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9B92
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9B93
Teleprotection Channel 2 Status
0 to 2
---
1
F134
1 (OK)
9B94
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9B95
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9BA0
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9BA1
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9BB0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9BC0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector switch actual values (read only)
A210
Selector switch 1 position
1 to 7
---
1
F001
0
A211
Selector switch 2 position
1 to 7
---
1
F001
1
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 65535
---
1
F300
0
A284
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A285
Selector 1 Acknowledge
0 to 65535
---
1
F300
0
A286
Selector 1 Bit0
0 to 65535
---
1
F300
0
A287
Selector 1 Bit1
0 to 65535
---
1
F300
0
A288
Selector 1 Bit2
0 to 65535
---
1
F300
0
A289
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28A
Selector 1 Bit Acknowledge
0 to 65535
---
1
F300
0
A28B
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A28C
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A28D
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 35 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...