B-12
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
1A04
Source 1 Phase CG Voltage RMS
V
F060
0
1A06
Source 1 Phase AG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A08
Source 1 Phase AG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A09
Source 1 Phase BG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0B
Source 1 Phase BG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0C
Source 1 Phase CG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0E
Source 1 Phase CG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0F
Source 1 Phase AB or AC Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A17
Source 1 Phase AB or AC Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A18
Source 1 Phase BC or BA Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1A
Source 1 Phase BC or BA Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1B
Source 1 Phase CA or CB Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1D
Source 1 Phase CA or CB Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1E
Source 1 Auxiliary Voltage RMS
V
F060
0
1A20
Source 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A22
Source 1 Auxiliary Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A23
Source 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A25
Source 1 Zero Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A26
Source 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A28
Source 1 Positive Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A29
Source 1 Negative Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A2B
Source 1 Negative Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A2C
Reserved (20 items)
---
---
---
F001
0
1A40
...Repeated for Source 2
1A80
...Repeated for Source 3
1AC0
...Repeated for Source 4
1B00
...Repeated for Source 5
1B40
...Repeated for Source 6
Source Power (Read Only) (6 modules)
1C00
Source 1 Three Phase Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C02
Source 1 Phase A Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C04
Source 1 Phase B Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C06
Source 1 Phase C Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C08
Source 1 Three Phase Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0A
Source 1 Phase A Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0C
Source 1 Phase B Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0E
Source 1 Phase C Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C10
Source 1 Three Phase Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C12
Source 1 Phase A Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C14
Source 1 Phase B Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C16
Source 1 Phase C Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C18
Source 1 Three Phase Power Factor
-0.999 to 1
---
0.001
F013
0
1C19
Source 1 Phase A Power Factor
-0.999 to 1
---
0.001
F013
0
Table B–9: MODBUS MEMORY MAP (Sheet 5 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...