B-28
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Frequency Out-Of-Band Accumulation (Read/Write Setting)
5F40
Frequency Out-Of-Band Accumulation Block
0 to 65535
---
1
F300
0
5F41
Frequency Out-Of-Band Accumulation Events
0 to 1
---
1
F102
0 (Disabled)
5F42
Frequency Out-Of-Band Accumulator 1 Function
0 to 1
---
1
F102
0 (Disabled)
5F43
Frequency Out-Of-Band Accumulator 2 Function
0 to 1
---
1
F102
0 (Disabled)
5F44
Frequency Out-Of-Band Accumulator 3 Function
0 to 1
---
1
F102
0 (Disabled)
5F45
Frequency Out-Of-Band Accumulator 4 Function
0 to 1
---
1
F102
0 (Disabled)
5F46
Frequency Out-Of-Band Accumulator 5 Function
0 to 1
---
1
F102
0 (Disabled)
5F47
Frequency Out-Of-Band Accumulator 6 Function
0 to 1
---
1
F102
0 (Disabled)
5F48
Frequency Out-Of-Band Accumulator 7 Function
0 to 1
---
1
F102
0 (Disabled)
5F49
Frequency Out-Of-Band Accumulator 1 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4A
Frequency Out-Of-Band Accumulator 2 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4B
Frequency Out-Of-Band Accumulator 3 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4C
Frequency Out-Of-Band Accumulator 4 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4D
Frequency Out-Of-Band Accumulator 5 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4E
Frequency Out-Of-Band Accumulator 6 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F4F
Frequency Out-Of-Band Accumulator 7 Lower Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F50
Frequency OOB Accumulation Minimum Volts/Amps
0.10 to 1.25
pu
0.01
F001
10
5F51
Frequency Out-Of-Band Accumulation Source
0 to 5
---
1
F167
0 (SRC 1)
5F52
Frequency Out-Of-Band Accumulation Target
0 to 2
---
1
F109
0 (Self-reset)
5F53
Frequency Out-Of-Band Accumulator 1 Time Limit
1 to 65535
s
1
F001
200
5F54
Frequency Out-Of-Band Accumulator 2 Time Limit
1 to 65535
s
1
F001
200
5F55
Frequency Out-Of-Band Accumulator 3 Time Limit
1 to 65535
s
1
F001
200
5F56
Frequency Out-Of-Band Accumulator 4 Time Limit
1 to 65535
s
1
F001
200
5F57
Frequency Out-Of-Band Accumulator 5 Time Limit
1 to 65535
s
1
F001
200
5F58
Frequency Out-Of-Band Accumulator 6 Time Limit
1 to 65535
s
1
F001
200
5F59
Frequency Out-Of-Band Accumulator 7 Time Limit
1 to 65535
s
1
F001
200
5F5A
Frequency Out-Of-Band Accumulator 1 Time Preset
0 to 65535
s
1
F001
0
5F5B
Frequency Out-Of-Band Accumulator 2 Time Preset
0 to 65535
s
1
F001
0
5F5C
Frequency Out-Of-Band Accumulator 3 Time Preset
0 to 65535
s
1
F001
0
5F5D
Frequency Out-Of-Band Accumulator 4 Time Preset
0 to 65535
s
1
F001
0
5F5E
Frequency Out-Of-Band Accumulator 5 Time Preset
0 to 65535
s
1
F001
0
5F5F
Frequency Out-Of-Band Accumulator 6 Time Preset
0 to 65535
s
1
F001
0
5F60
Frequency Out-Of-Band Accumulator 7 Time Preset
0 to 65535
s
1
F001
0
5F61
Frequency Out-Of-Band Accumulator 1 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F62
Frequency Out-Of-Band Accumulator 2 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F63
Frequency Out-Of-Band Accumulator 3 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F64
Frequency Out-Of-Band Accumulator 4 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F65
Frequency Out-Of-Band Accumulator 5 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F66
Frequency Out-Of-Band Accumulator 6 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
5F67
Frequency Out-Of-Band Accumulator 7 Upper Frequency
20.00 to 70.00
Hz
0.01
F001
6000
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F81
Setting Groups Block
0 to 65535
---
1
F300
0
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...