10 APPLICATION OF SETTINGS
10.1 SETTING EXAMPLE
10
To prevent maloperation for power swings the element is typically time delayed by 20 to 30 seconds. For sequential tripping
applications the time delay will be 2 to 3 seconds. The element may be blocked when the generator is offline. The line
source will be used for this application. Make the following changes in EnerVista UR Setup or through the
SETTINGS
ÖØ
GROUPED ELEMENTS
ÖØ
SETTING GROUP 1
ÖØ
SENSITIVE DIRECTIONAL POWER
Ö
DIRECTIONAL POWER 1
menu:
Sequential tripping logic can be implemented in FlexLogic™ as follows:
Figure 10–2: SEQUENTIAL TRIPPING FLEXLOGIC™
10.1.9 SYSTEM BACKUP OVERCURRENT
System backup protection is implemented using a phase time overcurrent element with voltage restraint enabled. The
NEUTRL source will be chosen for this element. The pickup of this element should be set at a safe margin above the max-
imum load expected on the machine.
(EQ 10.16)
The selection of all standard curves (and FlexCurves™) is allowed for easy coordination with system relaying. For the
example system, an IEEE extremely inverse curve will be used and a setting will be chosen such that the operate time for a
three phase fault on the high side of the transformer is 0.75 seconds. For simplicity, the power system contribution is not
considered.
(EQ 10.17)
(EQ 10.18)
(EQ 10.19)
(EQ 10.20)
(EQ 10.21)
The equation for an IEEE extremely inverse curve is as follows:
(EQ 10.22)
56
57
54
55
AND(2)
= SEQ TRIP (VO9)
DIR POWER 1 STG2 OP
INLET VALVE OFF(H8A)
AND(2)
= SEQ TRIP (VO9)
830731A1.CDR
PICKUP
1.5
Generator Nominal Current
CT Primary
------------------------------------------------------------------------
×
1.5
6800
8000
-------------
×
1.275 pu
=
=
=
Transformer Impedance
0.10
211.765
200
---------------------
×
0.106 pu on machine base
=
=
Impedance to Fault
0.216
0.106
+
0.322 pu
=
=
Fault Current
V
X
----
1
0.322
---------------
6800
8000
-------------
×
2.64 pu
=
=
=
Fault Voltage
Nominal Voltage
Transformer Impedance
Total Impedance
----------------------------------------------------------------
×
18 kV
10.6
32.2
-----------
×
5.93 kV
=
=
=
Pickup Reduction
Fault Voltage
Generator Nominal Voltage
------------------------------------------------------------------------
5.93 kV
18 kV
--------------------
0.329
=
=
=
T
TDM
A
I
I
pickup
Pickup Reduction
×
---------------------------------------------------------------------
⎝
⎠
⎛
⎞
p
1
–
---------------------------------------------------------------------------------------
B
+
×
=
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...