GE Multilin
G60 Generator Protection System
B-63
APPENDIX B
B.4 MEMORY MAPPING
B
EA52
PMU TCP port number
1 to 65535
---
1
F001
4712
EA53
PMU UDP port number 1
1 to 65535
---
1
F001
4713
EA54
PMU UDP port number 2
1 to 65535
---
1
F001
4714
Phasor Measurement Unit Basic Configuration (Read/Write Setting)
EA58
PMU 1 Function
0 to 1
---
1
F102
0 (Disabled)
EA59
PMU 1 IDcode
1 to 65534
---
1
F001
1
EA5A
PMU 1 STN
---
---
---
F203
“GE-UR-PMU”
EA62
PMU 1 Source
0 to 5
---
1
F167
0 (SRC 1)
EA63
PMU 1 Post-Filter
0 to 3
---
1
F540
1 (Symm-3-point)
Phasor Measurement Unit Calibration (Read/Write Setting)
EA88
PMU 1 Va Calibration Angle
-5 to 5
°
0.05
F002
0
EA89
PMU 1 Vb Calibration Angle
-5 to 5
°
0.05
F002
0
EA8A
PMU 1 Vc Calibration Angle
-5 to 5
°
0.05
F002
0
EA8B
PMU 1 Vx Calibration Angle
-5 to 5
°
0.05
F002
0
EA8C
PMU 1 Ia Calibration Angle
-5 to 5
°
0.05
F002
0
EA8D
PMU 1 Ib Calibration Angle
-5 to 5
°
0.05
F002
0
EA8E
PMU 1 Ic Calibration Angle
-5 to 5
°
0.05
F002
0
EA8F
PMU 1 Ig Calibration Angle
-5 to 5
°
0.05
F002
0
EA90
PMU 1 Sequence Voltage Shift Angle
-180 to 180
°
30
F002
0
EA91
PMU 1 Sequence Current Shift Angle
-180 to 180
°
30
F002
0
Phasor Measurement Unit Triggering (Read/Write Setting)
EAB0
PMU 1 User Trigger
0 to 65535
---
1
F300
0
Phasor Measurement Unit Current Trigger (Read/Write Setting)
EAB4
PMU 1 Current Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EAB5
PMU 1 Current Trigger Pickup
0.1 to 30
pu
0.001
F001
1800
EAB6
PMU 1 Current Trigger Pickup Time
0 to 600
s
0.01
F001
10
EAB7
PMU 1 Current Trigger Dropout Time
0 to 600
s
0.01
F001
100
EAB8
PMU 1 Current Trigger Block (3 items)
0 to 65535
---
1
F300
0
EABB
PMU 1 Current Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EABC
PMU 1 Current Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EAD8
PMU 1 df/dt Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EAD9
PMU 1 df/dt Trigger Raise
0.1 to 15
Hz/s
0.01
F001
25
EADA
PMU 1 df/dt Trigger Fall
0.1 to 15
Hz/s
0.01
F001
25
EADB
PMU 1 df/dt Trigger Pickup Time
0 to 600
s
0.01
F001
10
EADC
PMU 1 df/dt Trigger Dropout Time
0 to 600
s
0.01
F001
100
EADD
PMU 1 df/dt Trigger Block (3 items)
0 to 65535
---
1
F300
0
EAE0
PMU 1 df/dt Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EAE1
PMU 1 df/dt Trigger Events
0 to 1
---
1
F102
0 (Disabled)
EAE2
...Repeated for PMU 2
EAEC
...Repeated for PMU 3
EAF6
...Repeated for PMU 4
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00
PMU 1 Frequency Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB01
PMU 1 Frequency Trigger Low Frequency
20 to 70
Hz
0.01
F001
4900
EB02
PMU 1 Frequency Trigger High Frequency
20 to 70
Hz
0.01
F001
6100
EB03
PMU 1 Frequency Trigger Pickup Time
0 to 600
s
0.01
F001
10
EB04
PMU 1 Frequency Trigger Dropout Time
0 to 600
s
0.01
F001
100
EB05
PMU 1 Frequency Trigger Block (3 items)
0 to 65535
---
1
F300
0
EB08
PMU 1 Frequency Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB09
PMU 1 Frequency Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB28
PMU 1 Power Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB29
PMU 1 Power Trigger Active
0.25 to 3
pu
0.001
F001
1250
Table B–9: MODBUS MEMORY MAP (Sheet 56 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...