GE Multilin
G60 Generator Protection System
B-81
APPENDIX B
B.4 MEMORY MAPPING
B
F400
UR_UINT16: CT/VT BANK SELECTION
F491
ENUMERATION: ANALOG INPUT MODE
0 = Default Value, 1 = Last Known
F500
UR_UINT16: PACKED BITFIELD
First register indicates input/output state with bits 0 (MSB) to 15
(LSB) corresponding to input/output state 1 to 16. The second reg-
ister indicates input/output state with bits 0 to 15 corresponding to
input/output state 17 to 32 (if required) The third register indicates
input/output state with bits 0 to 15 corresponding to input/output
state 33 to 48 (if required). The fourth register indicates input/out-
put state with bits 0 to 15 corresponding to input/output state 49 to
64 (if required).
The number of registers required is determined by the specific
data item. A bit value of 0 = Off and 1 = On.
F501
UR_UINT16: LED STATUS
Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
the LED is on, 0 indicates the LED is off.
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element ID
X is bit [X mod 16] in register [X/16].
F504
BITFIELD: 3-PHASE ELEMENT STATE
F505
BITFIELD: CONTACT OUTPUT STATE
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected
F507
BITFIELD: COUNTER ELEMENT STATE
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than
F508
BITFIELD: DISTANCE ELEMENT STATE
F509
BITFIELD: SIMPLE ELEMENT STATE
0 = Operate
F511
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C
F513
ENUMERATION: POWER SWING MODE
0 = Two Step, 1 = Three Step
bitmask
bank selection
0
Card 1 Contact 1 to 4
1
Card 1 Contact 5 to 8
2
Card 2 Contact 1 to 4
3
Card 2 Contact 5 to 8
4
Card 3 Contact 1 to 4
5
Card 3 Contact 5 to 8
bitmask
element state
0
Pickup
1
Operate
2
Pickup Phase A
3
Pickup Phase B
4
Pickup Phase C
5
Operate Phase A
6
Operate Phase B
7
Operate Phase C
bitmask
distance element state
0
Pickup
1
Operate
2
Pickup AB
3
Pickup BC
4
Pickup CA
5
Operate AB
6
Operate BC
7
Operate CA
8
Timed
9
Operate IAB
10
Operate IBC
11
Operate ICA
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...