GE Multilin
G60 Generator Protection System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
66A2
Sensitive Directional Power 1 RCA
0 to 359
degrees
1
F001
0
66A3
Sensitive Directional Power 1 Calibration
0 to 0.95
degrees
0.05
F001
0
66A4
Sensitive Directional Power 1 STG1 SMIN
-1.2 to 1.2
pu
0.001
F002
100
66A5
Sensitive Directional Power 1 STG1 Delay
0 to 600
s
0.01
F001
50
66A6
Sensitive Directional Power 1 STG2 SMIN
-1.2 to 1.2
pu
0.001
F002
100
66A7
Sensitive Directional Power 1 STG2 Delay
0 to 600
s
0.01
F001
2000
66A8
Sensitive Directional Power 1 Block
---
---
---
F001
0
66A9
Sensitive Directional Power 1 Target
0 to 2
---
1
F109
0 (Self-reset)
66AA
Sensitive Directional Power 1 Events
0 to 1
---
1
F102
0 (Disabled)
66AB
Reserved (5 items)
0 to 65535
---
1
F001
0
66B0
...Repeated for Sensitive Directional Power 2
Third Harmonic Neutral Undervoltage (Read/Write Grouped Setting)
6730
Third Harmonic Neutral Undervoltage Function
0 to 1
---
1
F102
0 (Disabled)
6731
Third Harmonic Neutral Undervoltage Pickup
0 to 30
pu
0.0001
F003
3000
6733
Third Harmonic Neutral Undervoltage Delay
0 to 600
s
0.01
F001
0
6734
Third Harmonic Neutral Undervoltage Max Power
0 to 30
pu
0.001
F003
200
6736
Third Harmonic Neutral Undervoltage Min Power
0 to 30
pu
0.001
F003
200
6738
Third Harmonic Neutral Undervoltage Volt Supervision
0 to 1.25
pu
0.001
F001
500
6739
Third Harmonic Neutral Undervoltage Block
0 to 65535
---
1
F300
0
673A
Third Harmonic Neutral Undervoltage Target
0 to 2
---
1
F109
0 (Self-reset)
673B
Third Harmonic Neutral Undervoltage Events
0 to 1
---
1
F102
0 (Disabled)
673C
Reserved (4 items)
0 to 65535
---
1
F001
0
Generator Unbalance (Read/Write Grouped Setting)
6740
Generator Unbalance Function
0 to 1
---
1
F102
0 (Disabled)
6741
Generator Unbalance Source
0 to 5
---
1
F167
0 (SRC 1)
6742
Generator Unbalance Source
0 to 1.25
pu
0.001
F001
800
6743
Generator Unbalance Stage 1 Pickup
0 to 100
%
0.01
F001
800
6744
Generator Unbalance Stage 1 K value
0 to 100
---
0.01
F001
100
6745
Generator Unbalance Stage 1 Tmin
0 to 50
s
0.001
F001
250
6746
Generator Unbalance Stage 1 Tmax
0 to 1000
s
0.1
F001
6000
6747
Generator Unbalance Stage 1 K Reset
0 to 1000
s
0.1
F001
2400
6748
Generator Unbalance Stage 2 Pickup
0 to 100
%
0.01
F001
300
6749
Generator Unbalance Stage 2 Pickup Delay
0 to 1000
s
0.1
F001
50
674A
Generator Unbalance Block
0 to 65535
---
1
F300
0
674B
Generator Unbalance Target
0 to 2
---
1
F109
0 (Self-reset)
674C
Generator Unbalance Events
0 to 1
---
1
F102
0 (Disabled)
674D
Reserved (3 items)
0 to 65535
---
1
F001
0
Stator Ground Source (Read/Write Grouped Setting)
6750
Stator Ground Source
0 to 5
---
1
F167
0 (SRC 1)
Stator Ground (Read/Write Grouped Setting)
6780
Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
6781
Stator Ground Stage 1 Pickup
0 to 0.900
pu
0.001
F001
150
6782
Stator Ground Stage 1 Pickup Delay
0 to 600
s
0.01
F001
100
6783
Stator Ground Stage 1 Supervision
0.001 to 0.100
pu
0.0001
F001
57
6784
Stator Ground Stage 2 Pickup
0 to 0.900
pu
0.001
F001
150
6785
Stator Ground Stage 2 Pickup Delay
0 to 600
s
0.01
F001
0
6786
Stator Ground Stage 2 Supervision
0.001 to 0.100
pu
0.0001
F001
45
6787
Stator Ground Block
---
---
---
F001
0
6788
Stator Ground Target
0 to 2
---
1
F109
0 (Self-reset)
6789
Stator Ground Event
0 to 1
---
1
F102
0 (Disabled)
678A
Reserved (5 items)
0 to 65535
---
1
F001
0
Split Phase Protection (Read/Write Grouped Setting)
67A0
Split Phase Protection Function
0 to 1
---
1
F102
0 (Disabled)
67A1
Split Phase Protection Source
0 to 5
---
1
F167
0 (SRC1)
Table B–9: MODBUS MEMORY MAP (Sheet 24 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...