B-20
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4192
Data Logger Trigger
0 to 65535
---
1
F300
0
4193
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
0 to 235959
---
1
F050
0
Clock (Read/Write Setting)
41A2
SR Date Format
0 to 4294967295
---
1
F051
0
41A4
SR Time Format
0 to 4294967295
---
1
F052
0
41A6
IRIG-B Signal Type
0 to 2
---
1
F114
0 (None)
41A7
Clock Events Enable / Disable
0 to 1
---
1
F102
0 (Disabled)
41A8
Time Zone Offset from UTC
–24 to 24
hours
0.5
F002
0
41A9
Daylight Savings Time (DST) Function
0 to 1
---
1
F102
0 (Disabled)
41AA
Daylight Savings Time (DST) Start Month
0 to 11
---
1
F237
0 (January)
41AB
Daylight Savings Time (DST) Start Day
0 to 6
---
1
F238
0 (Sunday)
41AC
Daylight Savings Time (DST) Start Day Instance
0 to 4
---
1
F239
0 (First)
41AD
Daylight Savings Time (DST) Start Hour
0 to 23
---
1
F001
2
41AE
Daylight Savings Time (DST) Stop Month
0 to 11
---
1
F237
0 (January)
41AF
Daylight Savings Time (DST) Stop Day
0 to 6
---
1
F238
0 (Sunday)
41B0
Daylight Savings Time (DST) Stop Day Instance
0 to 4
---
1
F239
0 (First)
41B1
Daylight Savings Time (DST) Stop Hour
0 to 23
---
1
F001
2
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
1 to 64
---
1
F001
5
41C1
Oscillography Trigger Mode
0 to 1
---
1
F118
0 (Auto. Overwrite)
41C2
Oscillography Trigger Position
0 to 100
%
1
F001
50
41C3
Oscillography Trigger Source
0 to 65535
---
1
F300
0
41C4
Oscillography AC Input Waveforms
0 to 4
---
1
F183
2 (16 samples/cycle)
41D0
Oscillography Analog Channel
n
(16 items)
0 to 65535
---
1
F600
0
4200
Oscillography Digital Channel
n
(63 items)
0 to 65535
---
1
F300
0
Trip and Alarm LEDs (Read/Write Setting)
4260
Trip LED Input FlexLogic Operand
0 to 65535
---
1
F300
0
4261
Alarm LED Input FlexLogic Operand
0 to 65535
---
1
F300
0
User Programmable LEDs (Read/Write Setting) (48 modules)
4280
FlexLogic™ Operand to Activate LED
0 to 65535
---
1
F300
0
4281
User LED type (latched or self-resetting)
0 to 1
---
1
F127
1 (Self-Reset)
4282
...Repeated for User-Programmable LED 2
4284
...Repeated for User-Programmable LED 3
4286
...Repeated for User-Programmable LED 4
4288
...Repeated for User-Programmable LED 5
428A
...Repeated for User-Programmable LED 6
428C
...Repeated for User-Programmable LED 7
428E
...Repeated for User-Programmable LED 8
4290
...Repeated for User-Programmable LED 9
4292
...Repeated for User-Programmable LED 10
4294
...Repeated for User-Programmable LED 11
4296
...Repeated for User-Programmable LED 12
4298
...Repeated for User-Programmable LED 13
429A
...Repeated for User-Programmable LED 14
429C
...Repeated for User-Programmable LED 15
429E
...Repeated for User-Programmable LED 16
42A0
...Repeated for User-Programmable LED 17
42A2
...Repeated for User-Programmable LED 18
42A4
...Repeated for User-Programmable LED 19
42A6
...Repeated for User-Programmable LED 20
42A8
...Repeated for User-Programmable LED 21
42AA
...Repeated for User-Programmable LED 22
Table B–9: MODBUS MEMORY MAP (Sheet 13 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...