![GE G60 UR Series Instruction Manual Download Page 553](http://html.mh-extra.com/html/ge/g60-ur-series/g60-ur-series_instruction-manual_130363553.webp)
GE Multilin
G60 Generator Protection System
B-71
APPENDIX B
B.4 MEMORY MAPPING
B
F125
ENUMERATION: ACCESS LEVEL
0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F130
ENUMERATION: SIMULATION MODE
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F135
ENUMERATION: GAIN CALIBRATION
0 = 0x1, 1 = 1x16
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F138
ENUMERATION: OSCILLOGRAPHY FILE TYPE
0 = Data File, 1 = Configuration File, 2 = Header File
F140
ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE,
DISABLED
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V,
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A,
6 = Notched 2 A
F141
ENUMERATION: SELF TEST ERRORS
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communcations Failure
9
Voltage Monitor
10
FlexLogic Error Token
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
16
Ethernet Switch Fail
17
Maintenance Alert 01
18
SNTP Failure
19
---
20
Primary Ethernet Fail
21
Secondary Ethernet Fail
22
Temperature Monitor
23
Process Bus Trouble
24
Brick Trouble
25
Field RTD Trouble
26
Field TDR Trouble
27
Remote Device Offline
28
Direct Device Offline
29
Direct Input/Output Ring Break
30
Any Minor Error
31
Any Major Error
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...