B-64
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
EB2A
PMU 1 Power Trigger Reactive
0.25 to 3
pu
0.001
F001
1250
EB2B
PMU 1 Power Trigger Apparent
0.25 to 3
pu
0.001
F001
1250
EB2C
PMU 1 Power Trigger Pickup Time
0 to 600
s
0.01
F001
10
EB2D
PMU 1 Power Trigger Dropout Time
0 to 600
s
0.01
F001
100
EB2E
PMU 1 Power Trigger Block (3 items)
0 to 65535
---
1
F300
0
EB31
PMU 1 Power Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB32
PMU 1 Power Trigger Events
0 to 1
---
1
F102
0 (Disabled)
EB33
...Repeated for PMU 2
EB3E
...Repeated for PMU 3
EB49
...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
EB54
PMU 1 Voltage Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB55
PMU 1 Voltage Trigger Low Voltage
0.25 to 1.25
pu
0.001
F001
800
EB56
PMU 1 Voltage Trigger High Voltage
0.75 to 1.75
pu
0.001
F001
1200
EB57
PMU 1 Voltage Trigger Pickup Time
0 to 600
s
0.01
F001
10
EB58
PMU 1 Voltage Trigger Dropout Time
0 to 600
s
0.01
F001
100
EB59
PMU 1 Voltage Trigger Block (3 items)
0 to 65535
---
1
F300
0
EB5C
PMU 1 Voltage Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB5D
PMU 1 Voltage Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
EB82
PMU One-shot Function
0 to 1
---
1
F102
0 (Disabled)
EB83
PMU One-shot Sequence Number
0 to 59
---
1
F001
1
EB84
PMU One-shot Time
0 to 235959
---
1
F050
0
Phasor Measurement Unit Test Values (Read/Write Setting)
EB86
PMU 1 Test Function
0 to 1
---
1
F102
0 (Disabled)
EB87
PMU 1 Phase A Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
EB89
PMU 1 Phase A Voltage Test Angle
-180 to 180
°
0.05
F002
0
EB8A
PMU 1 Phase B Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
EB8C
PMU 1 Phase B Voltage Test Angle
-180 to 180
°
0.05
F002
-120
EB8D
PMU 1 Phase C Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
EB8F
PMU 1 Phase C Voltage Test Angle
-180 to 180
°
0.05
F002
120
EB90
PMU 1 Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
EB92
PMU 1 Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
EB93
PMU 1 Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
EB95
PMU 1 Phase A Current Test Angle
-180 to 180
°
0.05
F002
-10
EB96
PMU 1 Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
EB98
PMU 1 Phase B Current Test Angle
-180 to 180
°
0.05
F002
-130
EB99
PMU 1 Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
EB9B
PMU 1 Phase C Current Test Angle
-180 to 180
°
0.05
F002
110
EB9C
PMU 1 Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
EB9E
PMU 1 Ground Current Test Angle
-180 to 180
°
0.05
F002
0
EB9F
PMU 1 Test Frequency
20 to 70
Hz
0.001
F003
60000
EBA1
PMU 1 Test df/dt
-10 to 10
Hz/s
0.001
F002
0
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command)
EBF6
PMU 1 Recorder Clear Configuration Counter
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit Recording Values (Read Only)
EBFA
PMU 1 Available Records
0 to 65535
---
1
F001
0
EBFB
PMU 1 Second Per Record
0 to 6553.5
---
0.1
F001
0
EBFD
PMU 1 Last Cleared Date
0 to 400000000
---
1
F050
0
Setting file template values (read only)
ED00
FlexLogic™ displays active
0 to 1
---
1
F102
1 (Enabled)
ED01
Reserved (6 items)
---
---
---
---
---
ED07
Last settings change date
0 to 4294967295
---
1
F050
0
ED09
Template bitmask (750 items)
0 to 65535
---
1
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 57 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...