5.7 CONTROL ELEMENTS
5 SETTINGS
5
5.7.7 FREQUENCY RATE OF CHANGE
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
FREQUENCY RATE OF CHANGE
Ö
FREQUENCY RATE OF CHANGE 1(4)
Four (4) independent rate of change of frequency elements are available. The element responds to rate of change of fre-
quency with voltage, current and frequency supervision.
•
FREQ RATE 1 TREND:
This setting allows configuring the element to respond to increasing or decreasing frequency,
or to frequency change in either direction.
•
FREQ RATE 1 PICKUP:
This setting specifies an intended
pickup threshold. For applications monitoring a
decreasing trend, set
FREQ RATE 1 TREND
to “Decreasing” and specify the pickup threshold accordingly. The operating
condition is:
.
For applications monitoring an increasing trend, set
FREQ RATE 1 TREND
to “Increasing” and specify the pickup thresh-
old accordingly. The operating condition is:
.
For applications monitoring rate of change of frequency in any direction set
FREQ RATE 1 TREND
to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is:
•
FREQ RATE 1 OV SUPV PICKUP:
This setting defines minimum voltage level required for operation of the element.
The supervising function responds to the positive-sequence voltage. Overvoltage supervision should be used to pre-
vent operation under specific system conditions such as faults.
•
FREQ RATE 1 OC SUPV PICKUP:
This setting defines minimum current level required for operation of the element.
The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set
the pickup threshold to zero if no overcurrent supervision is required.
FREQUENCY RATE
OF CHANGE 1
FREQ RATE 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
FREQ RATE 1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
FREQ RATE 1 TREND:
Decreasing
Range: Increasing, Decreasing, Bi-directional
MESSAGE
FREQ RATE 1 PICKUP:
0.50 Hz/sec
Range: 0.10 to 15.00 Hz/sec in steps of 0.01
MESSAGE
FREQ RATE 1 OV SUPV
PICKUP: 0.700 pu
Range: 0.100 to 3.000 pu in steps of 0.001
MESSAGE
FREQ RATE 1 OC SUPV
PICKUP: 0.200 pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
FREQ RATE 1 MIN
FREQUENCY: 45.00 Hz
Range: 20.00 to 80.00 Hz in steps of 0.01
MESSAGE
FREQ RATE 1 MAX
FREQUENCY: 65.00 Hz
Range: 20.00 to 80.00 Hz in steps of 0.01
MESSAGE
FREQ RATE 1 PICKUP
DELAY: 0.000 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
FREQ RATE 1 RESET
DELAY: 0.000 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
FREQ RATE 1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
FREQ RATE 1 TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
FREQ RATE 1 EVENTS:
Disabled
Range: Disabled, Enabled
df dt
⁄
df dt
⁄
–
Pickup
>
df dt
⁄
Pickup
>
abs
df dt
⁄
(
)
Pickup
>
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...