5-176
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–95: SPLIT PHASE PROTECTION OPERATING CHARACTERISTICS
•
SPLIT PHASE SOURCE
: This setting specifies a signal source used to provide current from the split phase CT to the
split phase protection.
•
SPLIT PHASE LOAD SOURCE
: This setting specifies a signal source used to provide current from the load CT to the
split phase protection.
•
SPLIT PHASE A(C) PICKUP
: This setting specifies a pickup level for each phase. This should be set less than the
minimum expected unbalance (split phase) current due to an inter-turn fault.
•
SPLIT PHASE A(C) OFFSET
: This setting specifies the steady-state split phase current at no-load for the each phase.
This should be set equal to the split phase current during normal (unfaulted) operation. The user should assign the split
phase current and the load current (positive sequence) to the data logger to identify the optimum value for this setting.
•
SPLIT PHASE A(C) SLOPE
: This setting specifies the slope of split phase characteristic for each phase. This setting
is used to bias the pickup of the element due to variations in generator loading. The slope is defined as the ratio of the
830729A1.CDR
Iload (pu)
I
spl
t
p
hs
(pu)
Offset
Slope
Operate
Operate
Min Load
Operating Characteristic
Iload (pu)
I
spl
t
p
hs
(pu)
Offset
Slope
Operate
Min Load
Operating Characteristic (mode = over)
Iload (pu)
I
spl
t
phs
(pu)
Operate
Operating Characteristic (mode = over, Min Load = 0, Slope = 0)
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...