GE Multilin
G60 Generator Protection System
B-23
APPENDIX B
B.4 MEMORY MAPPING
B
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47AA
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AB
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AC
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
47AD
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
47AE
Synchrocheck 1 Block
0 to 65535
---
1
F300
0
47AF
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
47B0
...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
48F0
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
““
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
User Programmable Pushbuttons (Read/Write Setting) (12 modules)
4E00
User Programmable Pushbutton 1 Function
0 to 2
---
1
F109
2 (Disabled)
4E01
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
4E0B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
4E15
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
4E1F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
4E20
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
4E21
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
4E22
User Programmable Pushbutton 1 LED Operand
0 to 65535
---
1
F300
0
4E23
User Programmable Pushbutton 1 Autoreset Delay
0 to 600
s
0.05
F001
0
4E24
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
4E25
User Programmable Pushbutton 1 Local Lock
0 to 65535
---
1
F300
0
4E26
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
4E27
User Programmable Pushbutton 1 Remote Lock
0 to 65535
---
1
F300
0
4E28
User Programmable Pushbutton 1 Reset
0 to 65535
---
1
F300
0
4E29
User Programmable Pushbutton 1 Set
0 to 65535
---
1
F300
0
4E2A
...Repeated for User Programmable Pushbutton 2
4E54
...Repeated for User Programmable Pushbutton 3
4E7E
...Repeated for User Programmable Pushbutton 4
4EA8
...Repeated for User Programmable Pushbutton 5
Table B–9: MODBUS MEMORY MAP (Sheet 16 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...