![GE G60 UR Series Instruction Manual Download Page 500](http://html.mh-extra.com/html/ge/g60-ur-series/g60-ur-series_instruction-manual_130363500.webp)
B-18
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Preferences (Read/Write Setting)
404F
Language
0 to 3
---
1
F531
0 (English)
4050
Flash Message Time
0.5 to 10
s
0.1
F001
10
4051
Default Message Timeout
10 to 900
s
1
F001
300
4052
Default Message Intensity
0 to 3
---
1
F101
0 (25%)
4053
Screen Saver Feature
0 to 1
---
1
F102
0 (Disabled)
4054
Screen Saver Wait Time
1 to 65535
min
1
F001
30
4055
Current Cutoff Level
0.002 to 0.02
pu
0.001
F001
20
4056
Voltage Cutoff Level
0.1 to 1
V
0.1
F001
10
Remote RTD Communications (Read/Write Setting)
407B
RRTD Slave Address
1 to 254
---
1
F001
254
407C
RRTD Baud Rate
0 to 4
---
1
F602
4 (19200)
407D
COM2 Selection
0 to 1
---
1
F601
0 (RS485)
Communications (Read/Write Setting)
407E
COM1 minimum response time
0 to 1000
ms
10
F001
0
407F
COM2 minimum response time
0 to 1000
ms
10
F001
0
4080
Modbus Slave Address
1 to 254
---
1
F001
254
4083
RS485 Com1 Baud Rate
0 to 11
---
1
F112
8 (115200)
4084
RS485 Com1 Parity
0 to 2
---
1
F113
0 (None)
4085
RS485 Com2 Baud Rate
0 to 11
---
1
F112
8 (115200)
4086
RS485 Com2 Parity
0 to 2
---
1
F113
0 (None)
4087
IP Address
0 to 4294967295
---
1
F003
56554706
4089
IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
408B
Gateway IP Address
0 to 4294967295
---
1
F003
56554497
408D
Network Address NSAP
---
---
---
F074
0
409A
DNP Channel 1 Port
0 to 4
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 4
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409D
Reserved
0 to 1
---
1
F001
0
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
1 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
1 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
1 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
1 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP unsolicited responses maximum retries
1 to 255
---
1
F001
10
40AC
DNP unsolicited responses destination address
0 to 65519
---
1
F001
1
40AD
Ethernet operation mode
0 to 1
---
1
F192
0 (Half-Duplex)
40AE
DNP current scale factor
0 to 8
---
1
F194
2 (1)
40AF
DNP voltage scale factor
0 to 8
---
1
F194
2 (1)
40B0
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B1
DNP energy scale factor
0 to 8
---
1
F194
2 (1)
40B2
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B3
DNP other scale factor
0 to 8
---
1
F194
2 (1)
40B4
DNP current default deadband
0 to 65535
---
1
F001
30000
40B6
DNP voltage default deadband
0 to 65535
---
1
F001
30000
40B8
DNP power default deadband
0 to 65535
---
1
F001
30000
40BA
DNP energy default deadband
0 to 65535
---
1
F001
30000
40BE
DNP other default deadband
0 to 65535
---
1
F001
30000
40C0
DNP IIN time synchronization bit period
1 to 10080
min
1
F001
1440
40C1
DNP message fragment size
30 to 2048
---
1
F001
240
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...