B-30
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
65C8
Power Swing Detect Outer Limit Angle
40 to 140
degrees
1
F001
120
65C9
Power Swing Detect Middle Limit Angle
40 to 140
degrees
1
F001
90
65CA
Power Swing Detect Inner Limit Angle
40 to 140
degrees
1
F001
60
65CB
Power Swing Detect Delay 1 Pickup
0 to 65.535
s
0.001
F001
30
65CC
Power Swing Detect Delay 1 Reset
0 to 65.535
s
0.001
F001
50
65CD
Power Swing Detect Delay 2 Pickup
0 to 65.535
s
0.001
F001
17
65CE
Power Swing Detect Delay 3 Pickup
0 to 65.535
s
0.001
F001
9
65CF
Power Swing Detect Delay 4 Pickup
0 to 65.535
s
0.001
F001
17
65D0
Power Swing Detect Seal In Delay
0 to 65.535
s
0.001
F001
400
65D1
Power Swing Detect Trip Mode
0 to 1
---
1
F514
0 (Delayed)
65D2
Power Swing Detect Block
0 to 65535
---
1
F300
0
65D3
Power Swing Detect Target
0 to 2
---
1
F109
0 (Self-reset)
65D4
Power Swing Detect Event
0 to 1
---
1
F102
0 (Disabled)
65D5
Power Swing Detect Shape
0 to 1
---
1
F085
0 (Mho Shape)
65D6
Power Swing Detect Quad Forward Middle
0.1 to 500
ohms
0.01
F001
6000
65D7
Power Swing Detect Quad Forward Outer
0.1 to 500
ohms
0.01
F001
7000
65D8
Power Swing Detect Quad Reverse Middle
0.1 to 500
ohms
0.01
F001
6000
65D9
Power Swing Detect Quad Reverse Outer
0.1 to 500
ohms
0.01
F001
7000
65DA
Power Swing Detect Outer Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DB
Power Swing Detect Outer Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DC
Power Swing Detect Middle Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DD
Power Swing Detect Middle Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DE
Power Swing Detect Inner Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DF
Power Swing Detect Inner Left Blinder
0.1 to 500
ohms
0.01
F001
10000
Accidental Energization (Read/Write Grouped Setting)
6660
Accidental Energization Function
0 to 1
---
1
F102
0 (Disabled)
6661
Accidental Energization Source
0 to 5
---
1
F167
0 (SRC 1)
6662
Accidental Energization Arming Mode
0 to 1
---
1
F193
0 (UV AND OFFLINE)
6663
Accidental Energization OC Pickup
0 to 3
---
0.001
F003
300
6665
Accidental Energization UV Pickup
0 to 3
---
0.001
F003
500
6667
Accidental Energization Offline
0 to 65535
---
1
F300
0
6668
Accidental Energization Block
0 to 65535
---
1
F300
0
6669
Accidental Energization Target
0 to 2
---
1
F109
0 (Self-reset)
666A
Accidental Energization Events
0 to 1
---
1
F102
0 (Disabled)
666B
Reserved (5 items)
0 to 65535
---
1
F001
0
Loss of Excitation (Read/Write Grouped Setting)
6680
Loss Of Excitation Function
0 to 1
---
1
F102
0 (Disabled)
6681
Loss Of Excitation Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6682
Loss Of Excitation Center 1
0.1 to 300
ohm
0.01
F001
1000
6683
Loss Of Excitation Radius 1
0.1 to 300
ohm
0.01
F001
800
6684
Loss Of Excitation UV Supervision Enable 1
0 to 1
---
1
F102
1 (Enabled)
6685
Loss Of Excitation Pickup Delay 1
0 to 65.535
s
0.001
F001
50
6686
Loss Of Excitation Center 2
0.1 to 300
ohm
0.01
F001
1200
6687
Loss Of Excitation Radius 2
0.1 to 300
ohm
0.01
F001
1000
6688
Loss Of Excitation UV Supervision Enable 2
0 to 1
---
1
F102
1 (Enabled)
6689
Loss Of Excitation Pickup Delay 2
0 to 65.535
s
0.001
F001
500
668A
Loss Of Excitation UV Supervision
0 to 1.25
pu
0.001
F001
700
668B
Loss Of Excitation Block
0 to 65535
---
1
F300
0
668C
Loss Of Excitation Target
0 to 2
---
1
F109
0 (Self-reset)
668D
Loss Of Excitation Events
0 to 1
---
1
F102
0 (Disabled)
668E
Reserved (5 items)
0 to 65535
---
1
F001
0
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
66A0
Sensitive Directional Power 1 Function
0 to 1
---
1
F102
0 (Disabled)
66A1
Sensitive Directional Power 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...