B-32
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
67A2
Split Phase Protection Load Source
0 to 5
---
1
F167
0 (SRC1)
67A3
Split Phase Protection Phase A Pickup
0.020 to 1.500
pu
0.001
F001
200
67A4
Split Phase Protection Phase A Offset
0 to 1
pu
0.001
F001
0
67A5
Split Phase Protection Phase A Slope
0 to 100
%
0.1
F001
0
67A6
Split Phase Protection Phase B Pickup
0.020 to 1.500
pu
0.001
F001
200
67A7
Split Phase Protection Phase B Offset
0 to 1
pu
0.001
F001
0
67A8
Split Phase Protection Phase B Slope
0 to 100
%
0.1
F001
0
67A9
Split Phase Protection Phase C Pickup
0.020 to 1.500
pu
0.001
F001
200
67AA
Split Phase Protection Phase C Offset
0 to 1
pu
0.001
F001
0
67AB
Split Phase Protection Phase C Slope
0 to 100
%
0.1
F001
0
67AC
Split Phase Protection Minimum Load
0 to 1
pu
0.01
F001
0
67AD
Split Phase Protection Mode
0 to 1
---
1
F225
0 (Over)
67AE
Split Phase Protection Delay
0 to 65.535
s
0.001
F001
0
67AF
Split Phase Protection Block
0 to 65535
---
1
F300
0
67B0
Split Phase Protection Target
0 to 2
---
1
F109
0 (Self-Reset)
67B1
Split Phase Protection Events
0 to 1
---
1
F102
0 (Disabled)
67B2
Reserved (6 items)
0 to 65535
---
1
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 65535
---
1
F300
0
7007
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7008
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7009
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to Ground)
700A
Reserved (6 items)
0 to 1
---
1
F001
0
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 65535
---
1
F300
0
7046
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7047
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7048
Reserved (8 items)
0 to 1
---
1
F001
0
Distance (Read/Write Grouped Setting)
7060
Distance Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7061
Memory Duration
5 to 25
cycles
1
F001
10
7062
Force Self-Polarization
0 to 65535
---
1
F300
0
7062
Force Memory Polarization
0 to 65535
---
1
F300
0
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7071
Phase Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7076
Phase Distance Zone 1 Block
0 to 65535
---
1
F300
0
7077
Phase Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...