B-26
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Phase Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5900
Phase Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5901
Phase Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5902
Phase Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5903
Phase Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5904
Phase Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5905
Phase Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5906
Phase Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5907
Phase Time Overcurrent 1 Voltage Restraint
0 to 1
---
1
F102
0 (Disabled)
5908
Phase TOC 1 Block For Each Phase (3 items)
0 to 65535
---
1
F300
0
590B
Phase Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
590C
Phase Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
590D
Reserved (3 items)
0 to 1
---
1
F001
0
5910
...Repeated for Phase Time Overcurrent 2
5920
...Repeated for Phase Time Overcurrent 3
5930
...Repeated for Phase Time Overcurrent 4
5940
...Repeated for Phase Time Overcurrent 5
5950
...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5A01
Phase Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5A02
Phase Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5A03
Phase Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5A05
Phase IOC1 Block For Phase A
0 to 65535
---
1
F300
0
5A06
Phase IOC1 Block For Phase B
0 to 65535
---
1
F300
0
5A07
Phase IOC1 Block For Phase C
0 to 65535
---
1
F300
0
5A08
Phase Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5A09
Phase Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5A0A
Reserved (6 items)
0 to 1
---
1
F001
0
5A10
...Repeated for Phase Instantaneous Overcurrent 2
5A20
...Repeated for Phase Instantaneous Overcurrent 3
5A30
...Repeated for Phase Instantaneous Overcurrent 4
5A40
...Repeated for Phase Instantaneous Overcurrent 5
5A50
...Repeated for Phase Instantaneous Overcurrent 6
5A60
...Repeated for Phase Instantaneous Overcurrent 7
5A70
...Repeated for Phase Instantaneous Overcurrent 8
5A80
...Repeated for Phase Instantaneous Overcurrent 9
5A90
...Repeated for Phase Instantaneous Overcurrent 10
5AA0
...Repeated for Phase Instantaneous Overcurrent 11
5AB0
...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5B01
Neutral Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5B02
Neutral Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5B03
Neutral Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5B04
Neutral Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5B05
Neutral Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5B06
Neutral Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5B07
Neutral Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
5B08
Neutral Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5B09
Neutral Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5B0A
Reserved (6 items)
0 to 1
---
1
F001
0
5B10
...Repeated for Neutral Time Overcurrent 2
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...