GE Multilin
G60 Generator Protection System
5-203
5 SETTINGS
5.7 CONTROL ELEMENTS
5
5.7.3 SETTING GROUPS
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
Ö
SETTINGS GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
GROUPED
ELEMENTS
settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The
SETTING GROUPS BLK
setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The
GROUP 2 ACTIVATE ON
to
GROUP 6 ACTIVATE ON
settings select a FlexLogic™ operand which, when set, will make the
particular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its
ACTIVATE ON
parameter takes priority over the lower-
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The
SETTING GROUP 1 NAME
to
SETTING GROUP 6 NAME
settings allows to user to assign a name to each of the six settings
groups. Once programmed, this name will appear on the second line of the
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(for example,
VIRTUAL INPUT 1 ON
) or from a local contact input (for example,
CONTACT IP 1 ON
) to initiate the use of a par-
ticular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned
VIRTUAL OUTPUT 1
operand is used to control the “On” state of a particular settings group.
SETTING GROUPS
SETTING GROUPS
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
SETTING GROUPS BLK:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 2 ACTIVATE ON:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 3 ACTIVATE ON:
Off
Range: FlexLogic™ operand
↓
MESSAGE
GROUP 6 ACTIVATE ON:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 1 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
GROUP 2 NAME:
Range: up to 16 alphanumeric characters
↓
MESSAGE
GROUP 6 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
SETTING GROUP
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...