GE Multilin
G60 Generator Protection System
5-215
5 SETTINGS
5.7 CONTROL ELEMENTS
5
b) ACCUMULATORS 1 TO 7
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
FREQUENCY OOB ACCUMULATION
Ö
FREQUENCY OOB ACCUMULATOR 1(7)
Seven frequency out-of-band accumulators are available. The following settings are available for each accumulator.
•
FREQ ACCUM 1 FUNCTION
: This setting enables and disabled a particular frequency band.
•
FREQ ACCUM 1 UPPER FREQ
: This setting specifies the upper frequency value, in Hz, below which band 1 values
start to accumulate. This upper frequency value must be greater than the lower frequency value.
•
FREQ ACCUM 1 LOWER FREQ
: This setting specifies the lower frequency value, in Hz, above which band 1 values
start to accumulate. This lower frequency value must be less than the upper frequency value.
•
FREQ ACCUM 1 TIME LIMIT
: This value specifies the accumulation time, in seconds, at which the overfrequency
accumulation band exceeds the overfrequency accumulation limit and operates.
•
FREQ ACCUM 1 TIME PRESET
: This setting allows the user to either transfer accumulated frequency time of opera-
tion values from a previous hardware platform to a new platform, or, given that some knowledge of the operation of the
turbine is known, to start accumulation at a user-specified value.
Figure 5–123: FREQUENCY OUT-OF-BAND ACCUMULATION LOGIC
FREQUENCY OOB
ACCUMULATOR 1
FREQ ACCUM 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
FREQ ACCUM 1 UPPER
FREQ 60.00 Hz
Range: 20 to 70 Hz in steps of 1
MESSAGE
FREQ ACCUM 1 LOWER
FREQ 60.00 Hz
Range: 20 to 70 Hz in steps of 1
MESSAGE
FREQ ACCUM 1 TIME
LIMIT: 200
s
Range: 1 to 65535 s in steps of 1
MESSAGE
FREQ ACCUM 1 TIME
PRESET: 0
s
Range: 0 to 65535 s in steps of 1
Accumulating
SETTING
= Off
FREQ ACCUM BLOCK
SETTING
= Volt/amp mag
FREQ OOB ACCUM
SOURCE
= Frequency
SETTING
= Enabled
FREQ ACCUM 1
FUNCTION
COMMANDS
RESET FREQ OOB
ACCUMULATORS
PRESET FREQ OOB
ACCUMULATORS
SETTING
V/A > MINIMUM
FREQ OOB ACCUM MIN
VOLT/AMP
AND
AND
f
LOWER
< f
f
UPPER
≤
SETTINGS
FREQ ACCUM 1 LOWER
FREQ
RUN
FREQ ACCUM 1 UPPER
FREQ
t
ACCUM
> t
LIMIT
SETTINGS
FREQ ACCUM 1 TIME
PRESET
RUN
FREQ ACCUM 1 TIME
LIMIT
ACTUAL VALUE
FREQ OOB BAND 1
ACCUMULATION
FLEXLOGIC OPERANDS
FREQ OOB BAND 1 OP
FREQ OOB BAND 1 DPO
FREQ OOB BAND 1 PKP
FLEXLOGIC OPERANDS
FREQ OOB BAND 2 OP
FREQ OOB BAND 3 OP
FREQ OOB BAND 4 OP
FREQ OOB BAND 5 OP
FREQ OOB BAND 6 OP
FREQ OOB BAND 7 OP
FLEXLOGIC OPERANDS
FREQ OOB BAND 2 PKP
FREQ OOB BAND 3 PKP
FREQ OOB BAND 4 PKP
FREQ OOB BAND 5 PKP
FREQ OOB BAND 6 PKP
FREQ OOB BAND 7 PKP
OR
OR
FLEXLOGIC OPERAND
FREQ OOB ACCUM PKP
FLEXLOGIC OPERAND
FREQ OOB ACCUM OP
830008A1.CDR
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...