GE Multilin
G60 Generator Protection System
10-7
10 APPLICATION OF SETTINGS
10.1 SETTING EXAMPLE
10
The zone 3 reach will be set at 120% of the generator transient reactance. The time delay of this element should be com-
pared to the generator decrement curve to verify the adequacy of this setting.
(EQ 10.27)
(EQ 10.28)
An mho shape has been chosen for this example. Therefore, the quadrilateral settings are left at their default values. Make
the following changes in EnerVista UR Setup or through the
SETTINGS
ÖØ
GROUPED ELEMENTS
ÖØ
SETTING GROUP 1
ÖØ
DISTANCE
Ö
PHASE DISTANCE Z1(3)
menus:
10.1.11 STATOR GROUND FAULT
a) AUXILIARY OVERVOLTAGE
Stator ground fault protection is implemented with an overvoltage element connected at the generator neutral resistor. The
auxiliary overvoltage element will be used in this example. The auxiliary voltage input has previously been assigned to the
NEUTRL source. In this example the element will be set to protect 97% of the stator against ground faults.
(EQ 10.29)
Generator impedance
X
d
V
L
2
MVA
G
----------------
×
j
1.967
18
(
)
2
211
--------------
×
j
3.01 primary ohms
=
=
=
Zone 3 reach
1.2
Generator impedance
CT ratio
VT ratio
---------------------
×
×
=
1.2
j
3.01
×
1600
157.5
---------------
×
=
j
36.68 secondary ohms
=
PICKUP
0.03
Nominal Phase
Ground Voltage
–
Ground VT Primary
----------------------------------------------------------------------------------------
×
0.03
18000
3
⁄
12000
----------------------------
×
0.026 pu
=
=
=
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...