background image

BE1-GPS100 

GENERATOR 

PROTECTION 

... 

,, 

The  BE1-GPS100  is a multifunction,  programmable numerical  protection,  meter,  and  control 
relay.  Functions  provided  include  three  phase  voltage  controlled,  voltage  restrained,  or 
standard  overcurrent,  phase  residual  and  independent  ground  overcurrent,  negative  sequence 
overcurrent,  breaker  failure,  over/underfrequency,  phase  over/undervoltage,  zero  sequence 

over/undervoltage,  and  negative  sequence overvoltage,  forward  or  reverse  power,  loss of 
excitation,  volts  per  hertz,  sync check,  sensitive  third  harmonic  ground  fault  monitoring,  breaker 
monitoring and  control  and metering  functions,  all in an integrated system. 

ADVANTAGES 

• 

BESTiogic provides  the  user  with  very  high  flexibility  in  configuring  a  protection and  control 

system. 

• 

Substantial  functionality  in  a  small  package,  useful where space is  very  limited  but  high 
functionality  is  needed. 

• 

Programmable  LCD  display  allows  the  relay  to  replace  local  indication and  control  func­

tions,  such  as  panel  metering,  alarm annunciation,  and  control  switches. 

• 

Three  independent  communication  ports  with  protocol  support allows  integration  with 

distributed  control  systems. 

• 

Provides  optional  separate  ground  current  input  for  those applications  where  this  is 
required. 

• 

Includes  frequency  tracking  and  voltage  restrained  overcurrent  for backup  and  cogenera­
tion  applications. 

• 

Includes  Real  Time Clock  with  8 hour  capacitor  ride  through  and  optional battery backup. 

• 

Available  in  fully  drawout half  rack  case.  Two  Basler  Electric half rack  IEDs  (Intelligent 
Electronic  Devices)  can  be dovetailed  together  to mount in  a  standard  19-inch  equipment 
rack with  no  special  mounting  hardware. 

• 

Available  in  fully drawout S1  case  with  test  paddle.  The  S1  case,  with  available adapter 
plates,  fits  cutout,  drilling and  behind  panel  projection  dimensions  for  common  Basler 

Electric,  GE  and  Westinghouse  unit  case  relays. 

WINDOWS®  SOFTWARE 

Interface  for  setting  and  communicating  with  Basler  protection  products. 
Request  BESTCOMS'"  for  BE1-GPS1 00. 

ADDITIONAL  INFORMATION 

INSTRUCTION  MANUAL 

Request  publication 

9318700990 

TIMING  CURVES 

Request  publication 

9252000999 

MOD8US 

lNS 

r;:;;tCTION MANUAL 

Request  publication 

9318700991 

DNP  3.0 

INSTRUCTlON MANUAL 

Request  publication 

9318700992 

§l 

Basler Electric 

P.  0.  BOX  269  HIGHLAND,  ILLINOIS,  U.S.A. 62249  PHONE  618-654·2341  FAX 618-654·2351 

SYSTEM 

FEATURES 

Pages 2 and 

APPLICATIONS 

Page 

FUNCTIONAL 

DESCRIPTION 

Pages 

4-6 

BESTiogic 

Pages 

and 

SPECIFICATIONS 

Pages 

7, 

10  - 11 

ORDERING 

INFORMATION 

Page 12 

UHQ-5 

11-01 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for BE-1-GPS100

Page 1: ...rrent input for those applications where this is required Includes frequency tracking and voltage restrained overcurrent for backup and cogenera tion applications Includes Real Time Clock with 8 hour...

Page 2: ...ic Fuse loss detection 60FL protects against false trip due to loss of voltage sensing CONTROL Virtual breaker control switch controllable from both HMI and com ports 101 Four virtual selector switche...

Page 3: ...1 Advanced HMI Human Machine Interface APPLICATIONS The BE1 GPS100 Generator Protection System provides three phase ground and negative sequence overcurrent voltage frequency reverse power loss of exc...

Page 4: ...ing the protection control metering and status monitoring functions into a substation automation system The standard IRIG 8 port provides time synchronization from a master clock Real time metering pr...

Page 5: ...and IG Used for Ground Differential Overcurrent CONTROL POWER CONTROL POWER NOTES BE1 GPS100 A6 POWER SUPPLY A7 B2 1 CONNECTIONS SHOWN ARE FOR USE WITH PRE PROGRAMMED LOGIC SCHEME LZ W 25 L Z W 25 PRO...

Page 6: ...E ENABLE ____ NOTES 8KRSTATUS CONDITIONING OSCI EVENT TRIGGER l SEAL IN LOGIC J m 1 ABBREVIATED LOGIC SHOWN E G NOT SHOWN THAT 27P 81 181 ARE CONTROLLED BY BKR STATUS 2 60FL ONLY SHOWN FOR V014 ALSO A...

Page 7: ...ulation Test for Electrical Relays Impulse and Dielectric Strength 2000Vac at 50 60Hz IEEE C37 90 1 1989 Standard Surge Withstand Cap ability Tests for Relays and Relay Systems Associated with Electri...

Page 8: ...g 3 1shot retrig 4 oscillator 5 integrating 6 latch Made J v INI BLK Mode v INI BLK _ Mode 0 disable 1 enable INI BLK 62 TIMER 162 TIMER 262 TIMER BREAKER FAILURE BF VT FUSE LOSS 60FL 62 162 cJ 62 60F...

Page 9: ...BKR r e _a SB LOGIC I _ COMMAND r CLOSED I____ r r RESET 1 I 1 TARGET I _ SG TARG L _ REPORTING SETTING 1 FUNCTION 1 4 __ r r RESET 1 I I ALARM I _ SA ALARM L _ REPORTING SETTING 1 FUNCTION 1 _I _4 __...

Page 10: ...000 12 0 2747 0 1042 1 000 0 4375 0 028 0 8868 V1 5 4678 0 10814 1 000 2 0469 0 028 5 5000 V2 4 4309 0 0991 1 000 1 9531 0 028 5 8231 E1 7 7624 0 02758 1 000 2 0938 0 028 7 7500 E2 4 9883 0 0129 1 000...

Page 11: ...Time Time Accuracy 1 Shot Non Retrig 1 Shot Retrig Integrating Latch 0 000 9999 Sec 0 5 or eye CURRENT PICKUP ACCURACY All 46 50 and 51 Phase andGround 5A 2 or S O mA Neutral and Negative Sequence 1A...

Page 12: ...ent Sensing Input Type B E or F or voltage sensing option to be 4 ASCII communication is standard on ComO fron1 RS 232 and Com1 rear RS 232 ports ffi Check with factory for availability ffi Aux VT inp...