BE1-GPS100
PERFORMANCE SPECIFICATIONS, continued
SYNC CHECK (25)
Delta Phase Angle:
1 - 25 degrees
Delta Voltage Magnitude: 1 - 20V
Delta Frequency:
0.01 - 0.50Hz
PHASE OVERIUNDERVOLTAGE
(27P, 127P,59P, 159P)
Mode:
1 of 3; 2 of 3; 3 of 3
Pickup:
1 0.0-300VL-L or 1 0.0-300VL-N
Delay Time:
0.050 - 600sec.
NEGATIVE SEQUENCE OVERVOLTAGE (47)
Pickup:
1.0 - 300VLN
Delay Time:
0.050 - 600sec.
AUXILIARY I 3VO OVERIUNDERVOLTAGE
(27X, 127X, 59X, 159X)
Mode:
Fundamental Vx, Phase 3V O,
3'd Harmonic Vx
Pickup:
1.0 - 150V
Delay Time:
0.050 - 600 Sec.
FREQUENCY (81, 181,281, 381)
Mode:
Over, Under
Pickup:
40.00 - 70.00 Hz
Delay Time:
0.000 - 600 Sec.
Time Accuracy:
±0.5% or
+
1 eye
I
-0 eye
(Min. trip time affected by minimum 3 eye
security count)
POWER (32, 132)
Mode:
Pickup:
Pickup Accuracy:
Delay Time:
Forward, Reverse
5A: 1.0 - 6000 Watts, 3 ph
1A: 1.0- 1200 Watts, 3 ph
±3%
0.050- 600 Sec.
UNDEREXCITATION (40Q, 140Q)
Pickup:
5A: 1.0- 6000 VARs, 3 ph
1A: 1.0- 1200 VARs, 3 ph
Pickup Accuracy: ±3%
Delay Time:
0.050 - 600 Sec.
GENERAL PURPOSE LOGIC TIMERS
(62, 162,262,362)
Mode:
PU.DO
T1 and T2 Delay Time:
Time Accuracy:
1 Shot, Non- Retrig.
1 Shot, Retrig.
Integrating
Latch
0.000- 9999 Sec.
±0.5% or ±%eye
CURRENT PICKUP ACCURACY (All 46, 50 and 51)
Phase and Ground:
5A
2% or S OmA
Neutral and Negative
Sequence:
1A
2% or 10mA
5A
3% or 75mA
1A
3% or 75mA
VOLTAGE PICKUP ACCURACY (All 27, 47 and 59)
±2% or ±0.5V
DEFINITE TIME ACCURACY UNLESS OTHERWISE
STATED (All 27, 32, 40Q, 47 and 59)
Definite Time Accuracy:
±0.5% or ± 1 eye
SETTING GROUPS
Setting Groups:
2
Control Modes:
External: Discrete input logic;
Binary: Input logic
METERING
Current Range:
5A
0.5 to 15.0
1A
0.1 to 3.0
Current Accuracy:
± 1%
Phase Voltage
Range:
Phase Voltage Accuracy:
3W
0 - 300 VL-L
4W
0 - 300 VL-L
o-
173 vl-N
±0.5% for
50V<VL-L <300V
Auxiliary Voltage Range:
0 - 150V
Auxiliary Voltage Accuracy: ±0.5% for
50V<V<150V
WattNAR:
Watt Accuracy:
VAR Accuracy:
5A
1A
0 to ±7500
0 to ±1500
1%@ Unity PF
1%@ Zero PF
Energy:
0 to ±1.0E12 (FIR
registers)
Frequency:
Frequency Accuracy:
10- 75Hz
0.01 Hz
DEMANDS (lA,
18,
IC, IN, IQ, Fwd Watts, Rvs Watts,
Fwd VARs, Rvs VARs)
Demand Interval: 1 - 60 min.
Demand Mode:
Thermal
BREAKER MONITORING
Duty Mode:
I or
F
Duty Alarm Range:
0 - to 100%
Op Counter Alarm Range: 0 - 99999
Trip Time Alarm Range:
20 - 1 OOOmSec
11
www
. ElectricalPartManuals