Basler BE-1-GPS100 Manual Download Page 7

BE1-GPS100 

GENERAL  SPECIFICATIONS 

Amp  CURRENT  INPUTS 

Continuous  rating: 
One  Sec.  Rating: 
Saturation  limit: 

Burden: 

1  Amp  CURRENT INPUTS 

20A 
400A 
150A 

< 1 Omilliohms 

Continuous rating: 

4A 

One  Sec.  rating: 

BOA 

Saturation limit: 

30A 

Burden: 

<22milliohms 

PHASE  AC  VOLTAGE  INPUTS 

Continuous: 

300V,  Line to  Line 

One  Sec.  rating: 
Burden: 

600V,  Line to Neutral 
Less than 1VA@ 300Vac 

AUXILIARY AC VOLTAGE  INPUT 

Continuous: 

150V 

One  Sec.  rating: 

600V 

Burden: 

Less than 1VA@ 150Vac 

A/D  CONVERTER 

Sampling  Rate: 

POWER  SUPPLY 

Option 1: 

Option 2: 

Option 3: 

Burden: 

TRIP  CONTACTS 

Make and carry: 
Continuous: 
Break: 

CONTROL  INPUTS 

12/cycle,  adjusted to 
input frequency  10-75Hz 

DC range 35 - 150V 
AC  range 55 - 135V 
DC range 90 - 300V 
AC range 90 - 270V 
DC range 17 - 32V  (down 
to 8V for momentary dips) 
6 watts continuous, 
8 watts maximum with 
all outputs energized 

30A  (0.2sec) 

?A 

0.3A DC  (L/R=0.04) 

Wetting voltage range:  Same as control power 

supply option. 

Low  Range 

High  Range 

Turn-on 

Turn-on 

Power  Supply 

Voltage 

Voltage 

Option 

Range 

Burden 

Range 

Burden 

1) 

48/125VacNdc 

26·38V 

13k  ohms 

69·100V 

24k  ohms 

2) 125/250VacNdc 

69·100V 

25k ohms 

138·200V 

54k ohms 

3)24Vdc 

5-8Vdc 

7k  ohms 

N/A 

N/A 

Control inputs recognize both DC and AC 

voltages. 

COMMUNICATION  PORTS 

Response time: 

< 1 OOmSec for metering 

and control functions 

Baud  rate: 

300 - 19200 

ELECTRICAL  ENVIRONMENT 

• 

IEEE C37.90-1989 Standard for  Relays and Relay 

Systems Associated with Electric Power Apparatus 

• 

IEC  255-5  Insulation Test for Electrical  Relays 
Impulse and Dielectric  Strength  (2000Vac at 50/60Hz) 

• 

IEEE C37.90.1-1989 Standard Surge Withstand Cap­

ability Tests for  Relays and  Relay Systems Associated 
with Electric Power Apparatus 

• 

IEC 255-22-1 1 MHz  Burst Disturbance Tests for  Elec­
trical  Disturbance  Tests  for  Measuring  Relays and 

Protection  Equipment 

• 

EN  61000-4-4 Electrical Fast Transient/Burst  Immunity 

Test 

• 

EN  61000-4-3  Radiated,  Radio-frequency,  Electro­
magnetic Field  Immunity Test 

• 

Type tested  using  a  5-watt,  hand-held  transceiver  in 

the ranges of 144 and 440MHz with the antenna 
placed within 6  inches of the relay. 

• 

IEEE C37.90.3  (Jan. 01) Draft Standard Electrostatic 

Discharge Tests for Protective  Relays 

• 

EN  61000-4-2  Electrostatic Discharge Immunity Test 

MECHANICAL  ENVIRONMENT 

• 

Operating temperature  range:  -40°C to 70°C* 

(-40°F  to  158°F) 

*LCD Display  is  inoperative  below  -20°C. 

• 

Storage temperature range:  -40°C  to  70°C 

(-40°F  to  158°F) 

• 

Humidity:  Qualified to  IEC 68-2-38,  1st  Edition 
1974,  Basic  Environmental  Test  Procedures, 
Part  2:  Test  Z/AD:  Composite Temperature 
Humidity  Cyclic Test 

• 

Qualified  to  IEC 255-21-1  (Class 1) Vibration Tests 
for  Electrical  Relays 

• 

Qualified to  IEC  255-21-2  (Class 1) Shock  and 

Bump Tests  for  Electrical  Relays 

CERTIFICATIONS 

UL  Recognized,  File  E97033 

CSA  Certified,  File LR23131 
DNP  3.0  lED  Certified,  Subset  Level  2,  6/20/00, 

by SUBNET Solutions,  Inc. 

CASE  SIZE 

H1:  10.50"W  x  3.47"H  x  9.10"D  with  mounting 

flanges  (8.5"W  without  mounting  flanges) 

S1:  6.65"W 

9.32"H 

9.405"D 

SHIPPING  WEIGHT 

H 1:  Approx.  1 0  pounds 
S1:  Approx.  16 pounds 

WARRANTY 

7  years 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for BE-1-GPS100

Page 1: ...rrent input for those applications where this is required Includes frequency tracking and voltage restrained overcurrent for backup and cogenera tion applications Includes Real Time Clock with 8 hour...

Page 2: ...ic Fuse loss detection 60FL protects against false trip due to loss of voltage sensing CONTROL Virtual breaker control switch controllable from both HMI and com ports 101 Four virtual selector switche...

Page 3: ...1 Advanced HMI Human Machine Interface APPLICATIONS The BE1 GPS100 Generator Protection System provides three phase ground and negative sequence overcurrent voltage frequency reverse power loss of exc...

Page 4: ...ing the protection control metering and status monitoring functions into a substation automation system The standard IRIG 8 port provides time synchronization from a master clock Real time metering pr...

Page 5: ...and IG Used for Ground Differential Overcurrent CONTROL POWER CONTROL POWER NOTES BE1 GPS100 A6 POWER SUPPLY A7 B2 1 CONNECTIONS SHOWN ARE FOR USE WITH PRE PROGRAMMED LOGIC SCHEME LZ W 25 L Z W 25 PRO...

Page 6: ...E ENABLE ____ NOTES 8KRSTATUS CONDITIONING OSCI EVENT TRIGGER l SEAL IN LOGIC J m 1 ABBREVIATED LOGIC SHOWN E G NOT SHOWN THAT 27P 81 181 ARE CONTROLLED BY BKR STATUS 2 60FL ONLY SHOWN FOR V014 ALSO A...

Page 7: ...ulation Test for Electrical Relays Impulse and Dielectric Strength 2000Vac at 50 60Hz IEEE C37 90 1 1989 Standard Surge Withstand Cap ability Tests for Relays and Relay Systems Associated with Electri...

Page 8: ...g 3 1shot retrig 4 oscillator 5 integrating 6 latch Made J v INI BLK Mode v INI BLK _ Mode 0 disable 1 enable INI BLK 62 TIMER 162 TIMER 262 TIMER BREAKER FAILURE BF VT FUSE LOSS 60FL 62 162 cJ 62 60F...

Page 9: ...BKR r e _a SB LOGIC I _ COMMAND r CLOSED I____ r r RESET 1 I 1 TARGET I _ SG TARG L _ REPORTING SETTING 1 FUNCTION 1 4 __ r r RESET 1 I I ALARM I _ SA ALARM L _ REPORTING SETTING 1 FUNCTION 1 _I _4 __...

Page 10: ...000 12 0 2747 0 1042 1 000 0 4375 0 028 0 8868 V1 5 4678 0 10814 1 000 2 0469 0 028 5 5000 V2 4 4309 0 0991 1 000 1 9531 0 028 5 8231 E1 7 7624 0 02758 1 000 2 0938 0 028 7 7500 E2 4 9883 0 0129 1 000...

Page 11: ...Time Time Accuracy 1 Shot Non Retrig 1 Shot Retrig Integrating Latch 0 000 9999 Sec 0 5 or eye CURRENT PICKUP ACCURACY All 46 50 and 51 Phase andGround 5A 2 or S O mA Neutral and Negative Sequence 1A...

Page 12: ...ent Sensing Input Type B E or F or voltage sensing option to be 4 ASCII communication is standard on ComO fron1 RS 232 and Com1 rear RS 232 ports ffi Check with factory for availability ffi Aux VT inp...