MCT-CM
166
Choose which loop value is to be retransmitted for the loop by pressing the appropriate function select button;
PV, SP or %Out. If ‘None’ is selected, the output will remain in the off state, i.e., 0Vdc or 4mA depending upon
the output type selection.
Enter the minimum and maximum values for which the output is to retransmit. The output range is -32760 to
32760 for a decimal point resolution of zero, -3276.0 to 3276.0 for a decimal point of one, -327.60 to 327.60 for
a decimal point of two and -32.760 to 32.760 for a decimal point resolution of three.
Once all settings have been made, press the ‘Save’ button to save the changes. If you do not press the ‘Save’
button, all changes will be lost if you leave the screen or navigate to another analog output.
10.6.1 Retransmitting Loop Percentage of Output
Depending upon the loop control being used, the percentage of output value for bimodal control (heat/cool) is
represented differently. For example, FDC 100 and 300 series controls represent heat output as a value from
0% to 100% while the cool output is represented as a value from 0% to -100%. Other controls supported by
the MCT may split the standard 0% to 100% range and use 50% to 100% for heating and 50% to 0% for cooling.
If the analog output is being used to control the position of a cooling valve or SCR power controller of a heater
bank for example, it is important that the analog output supply only the signal for the proper heating or cooling
range in order to properly control the amount of cooling or heating applied to a process.
The MCT provides the ability to supply only the heating output, cooling output or a combination of heating and
cooling outputs from its analog outputs. For example, if an FDC 300 series control is used, setting an
‘Out Min’
to ‘Out Max’ range of 0% to 100% will result in an analog output of 0-10Vdc or 4-20mA for an output of 0% to
100% heating. If a different model of controller is used that represents heating as 50% to 100% with cooling
from 50% to 0%, setting an
‘Out Min’ to ‘Out Max’ range of 50% to 100% will result in an analog output of 0-
10Vdc or 4-20mA for an output of 0% to 100% of the heat output.
In order to retransmit a cooling percentage of output, the MCT allows the analog output range to be inverted
relative to the value representing the cooling percentage of output. This allows the positioner of a cooling valve
for example, to receive a 0-10Vdc or 4-20mA signal representing 0% (full closed) to 100% (full open) of cooling
even if the cooling percentage represented by the controller is 50% (no cooling output) to 0% (full cooling
output).
For example, if 0% to -100% represents no cooling to full cooling, setting the
‘Out Min’ field to 0% and the ‘Out
Max’ field to -100% will produce an analog output of 0-10Vdc or 4-20mA for an output of 0% to 100% cooling.
If a model of controller is used that represents cooling as 50% to 0% while heating is represented as 50% to
100%, setting an
‘Out Min’ to ‘Out Max’ range of 50% to 0% will result in an analog output of 0-10Vdc or 4-
20mA for an output of 0% to 100% of the cool output.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...